37
Operang Instrucons - BPS2000v2 Monitoring Power Distribuon Unit
R
Registry name
Registry address
Unit
Access
W/R
Actual value
S
Size
Decimal
H
Hexadecimal
Smoke 61 0x003D R
1=Yes
2=No
2 Bytes
Water 62 0x003E R
1=Yes
2=No
2 Bytes
Low Alarm L1 Voltage 00063 0x003F V R/W =register/10 2 Bytes
High Alarm L1 Voltage 00064 0x0040 V R/W =register/10 2 Bytes
Low Alarm L2 Voltage 00065 0x0041 V R/W =register/10 2 Bytes
High Alarm L2 Voltage 00066 0x0042 V R/W =register/10 2 Bytes
Low Alarm L3 Voltage 00067 0x0043 V R/W =register/10 2 Bytes
High Alarm L3 Voltage 00068 0x0044 V R/W =register/10 2 Bytes
Low Alarm L1 Current 00069 0x0045 A R/W =register/10 2 Bytes
High Alarm L1 Current 00070 0x0046 A R/W =register/10 2 Bytes
Low Alarm L2 Current 00071 0x0047 A R/W =register/10 2 Bytes
High Alarm L2 Current 00072 0x0048 A R/W =register/10 2 Bytes
Low Alarm L3 Current 00073 0x0049 A R/W =register/10 2 Bytes
High Alarm L3 Current 00074 0x004A A R/W =register/10 2 Bytes
Low Alarm Temperature 00075 0x004B R/W =register 2 Bytes
High Alarm Temperature 00076 0x004C R/W =register 2 Bytes
Low Alarm Temperature1 00077 0x004B R/W =register 2 Bytes
High Alarm Temperature1 00078 0x004C R/W =register 2 Bytes
Low Alarm Temperature2 00079 0x004F R/W =register 2 Bytes
High Alarm Temperature2 00080 0x0050 R/W =register 2 Bytes
Modbus RTU/TCP memory map-connuaon