Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FUn-
Function menu (continued)
Stt-
Stop configuration menu
Stt
Type of stop
rMP
rMP
FSt
nSt
Stop mode on disappearance of the run command and appearance of a stop command
Ramp stop
Fast stop
Freewheel
nSt
Freewheel stop assignment
nO
nO
L1L
L2L
L3L
L4L
The stop is activated when the input or the bit changes to 0. If the input returns to state 1 and the run
command is still active, the motor will only restart if Type of control tCC page 47
= 2C and 2 wire type control
tCt page 50
= LEL or PFO. If not, a new run command must be sent.
Not assigned
L1L: LI1 Active Low to stop
L2L: LI2 Active Low to stop
L3L: LI3 Active Low to stop
L4L: LI4 Active Low to stop
FSt
Fast stop assignment
nO
nO
L1L
L2L
L3L
L4L
Not assigned
L1L: LI1 Active Low to stop
L2L: LI2 Active Low to stop
L3L: LI3 Active Low to stop
L4L: LI4 Active Low to stop
dCF
Ramp divider
1 to 10
4
Visible only if Fast stop assignment FSt page 61 is not set to nO or if FSt is set to Type of stop Stt page 64.
The ramp that is enabled (Deceleration dEC page 44
or Deceleration 2 dE2 page 63) is then divided by this
coefficient when stop requests are sent.
Value 10 corresponds to a minimum ramp time.
Code Name/Description Adjustment range Factory setting
FUn-
Function menu (continued)
rrS
Reverse direction
nO
nO
LIH
L2H
L3H
L4H
LI1 to LI4: choice of the input assigned to the reverse command
Function inactive
L1h: L1 active high
L2h: L2 active high
L3h: L3 active high
L4h: L4 active high
Parameter that can be modified during operation or when stopped.