65
Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FUn-
Function menu (continued)
AdC-
Auto DC injection menu
AdC
nO
YES
Ct
• Automatic DC injection
YES
• Function inactive, no DC injected current.
• Time limited DC injection
• Continuous DC injection
SdC1
• Automatic DC injection current
0 to 120% of nCr 70%
Visible only if Automatic DC injection AdC is not set to nO.
Injection current on stopping and continuous DC injection.
tdC1
• Automatic DC injection time
0.1 to 30 s 0.5 s
Visible only if Automatic DC injection AdC is not set to nO.
Injection time on stopping.
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-