Configuration Mode - Complete menu (FULL)
Code Name/Description Adjustment range Factory setting
FLt-
Fault detection management menu (continued)
SLL
• Modbus fault management
YES
nO
YES
Behavior of the drive in the event of a communication fault with integrated Modbus.
• Fault ignored
• Freewheel stop
WARNING
LOSS OF CONTROL
If Modbus fault mgt SLL is set to n0, communication control will be inhibited. For safety reasons, inhibition of
communication fault should only be used for adjustment or special applications purpose.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
drn
• Degraded line supply operation
nO
nO
YES
Lowers the tripping threshold of the USF fault to operate on a line supply down to 50% of nominal line
voltage. In this case, a line choke must be used and the performance of the drive controller cannot be
guaranteed
• nO
• Yes
rPr
nO
FtH
• Reset power run
nO
This reset will initialize the settings located on MOn section, menu MAI-, page 40.
• nO
• Reset fan time display
To change the assignment of this parameter press the “ENT” key for 2 s.
Parameter that can be modified during operation or when stopped.