91
Diagnostics and Troubleshooting
Faults codes that will be reset as soon as their causes disappear
The USF fault can be inhibited and cleared remotely by means of a logic input (Detected fault inhibition assignmentInH parameter page 81).
(1) When the CFI is present in the past fault menu, it means the configuration has been interrupted or is not fully finished.
HMI block changed
When an HMI block is replaced by an HMI block configured on a drive with a different rating, the drive locks in Incorrect configuration CFF
fault mode on power-up. If the card has been deliberately changed, the fault can be cleared by pressing the ENT key twice, which restores
all the factory settings.
Code Name Possible causes Remedy
CFF Incorrect
configuration
HMI block replaced by an HMI
block configured on a drive with a
different rating
The current configuration of
customer parameters is
inconsistent
Return to factory settings or retrieve the backup
configuration, if it is valid.
If the fault remains after reverting to the factory settings,
contact your local BLEMO representative
CFI
(1)
Invalid configuration Invalid configuration
The configuration loaded in the
drive via the bus or communication
network is inconsistent. The
configuration upload has been
interrupted or is not fully finished.
Check the configuration loaded previously.
Load a compatible configuration
CFI2 Download invalid
configuration
Interruption of download operation
with Loader or Software
Check connection with Loader or Software.
To reset the default re-start the download operation or
restore the factory setting
USF Undervoltage Line supply too low
Transient voltage dip
Check the voltage and the parameters of Undervoltage