6.6.7 Connect GRID and BACKUP Cables
Step 1: Prepare neutral wire, fire wire, and grounding wire (Blue, brown, yellow-green
outdoor multi-core copper cables, and RNB8-6 OT terminals are recommended.).
Strip the cables according to Figure 6-13-1.
Step 2: Insert the exposed core wires into the OT terminal and crimp them with a
crimper, as shown in Figure 6-13-2. Then, pull to confirm that the terminal crimping
is tight.
Step 3: Fix the terminals to EP760 inverter BACKUP and GRID areas with a cross
screwdriver as shown in Figure 6-13-3 and 6-13-4.
Step 4: Attach the PG waterproof connector to the AC cable protection case. Tighten
the hexagon nut of the connector with a socket tool, as shown in Figure 6-13-5.
Step 5: Pass the cable through the PG waterproof connector, as shown in Figure
6-13-6.
Step 6: Secure the AC cable protection case to the BACKUP and GRID areas with 6
M4 screws. Tighten the fitting clockwise to the protection case as shown in Figure
6-13-7.
Recommended torque: 1.2Nm
Figure 6-13-1 Figure 6-13-2
A=55~65mm
B=C+3mm
Visible wire
Wire even or bulge
up to 1mm