DUCTED REVERSE CYCLE REFRIGERATED AIR CONDITIONING
Page 22
Electrical
OUTDOOR UNIT CONNECTIONS
1. Install a dedicated circuit from the mains switch
board. Circuit breaker requirements as per table
below.
2. Connect the mains cables to the incoming
connection block on the outdoor unit
3. Connect the low voltage control cable from the
indoor unit to the comms port available on the
outdoor PCB.
Use supply wire sizes as per local electrical codes and regulations.
WIRING DIAGRAM - SINGLE PHASE INDOOR UNIT
Model
Recommended
Circuit Breaker
Full Load
Amps
Recommended
Cable Size
B007RS 25A 14.5 2.5mm
B009RS 32A 16.5 4.0mm
B012RS 32A 21.8 4.0mm
B015RS 40A 32.4 6.0mm
B016RT 3 x 32 A 14.8 4.0mm
B019RT 3 x 32 A 19.5 4.0mm
PLEASE NOTE: Circuit breaker and cable sizes are subject to cable run length – refer
AS 3000 wiring rules