EasyManua.ls Logo

Bongioanni Multidea Evo 60 - Connection of Outside Sensor (Optional)

Default Icon
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
b
WARNINGS
The following is compulsory:
Use of an omnipolar thermal magnetic circuit breaker, line disconnector, in compliance with EN standards.
Observance of the connections L (Phase) - N (Neutral).
Use of cable sections of AT LEAST 1 mm
2
.
Use of an earthing wire that is at least 2 cm longer than those of the L (Phase) - N (Neutral) connections.
Reference to the wiring diagrams included in this manual for any type of electrical intervention.
Connections to an efficient earthing system (*).
NEVER use water hoses for earthing the appliance.
Great care to observe maximum absorption levels of the external circulation pumps (see “WIRING DIAGRAM” page 14).
(*) The manufacturer declines all liability for any damage caused by failure to earth the appliance or specifications
in the wiring diagrams.
N.B. The on-board fuse is 3.15A both for Phase and Neutral.
REMOTE ALARM
The outputs of terminals 11-12 supply a voltage-free contact (max 230Vac - 0.8A) for the management of an alarm signal.
This contact is activated each time an error/malfunction occurs on the boiler.
CONNECTION OF OUTSIDE SENSOR (OPTIONAL)
The outside sensor must be installed on the outside of the building,
on a flat surface in a north/north-east position (the coolest side)
and at a safe distance from the flues, doors, windows and areas
exposed to direct sunlight.
To install, proceed as follows:
- Remove the cover.
- Fix the sensor to the wall using two plugs.
- Make the electrical connections.
NOTE:
- Minimum cable section: 1 mm
2
.
- Maximum connection length: 50 m.
- Non-polarised connection terminals.
- Use shielded coaxial cables, with 2 wires and connect the
sheath to earth.
- 23 -
INSTALLATION

Related product manuals