22
|
Installation Instructions
Bosch 15 SEER2 Inverter Ducted Packaged Heat Pump - BTC 761701319 A (12.2022)
WARNING: ELECTRICAL SHOCK
Label all wiring prior to disconnection when
servicing controls. Wiring errors can cause improper
and dangerous operation. Verify proper operation
after servicing.
Size (Tons) Volt
Compressors OD Fan Motors
Supply Blower
Motor
Unit Circuit
RLA LRA FLA FLA
MCA
(Amps)
Max Fuse Breaker
Size(Amps)
36 (3.0) 208/230-1-60 15.0 52.0 2.0 4.3 25.1 40
60 (5.0) 208/230-1-60 27.0 61.0 2.0 5.9 41.7 60
Table 12 Electrical Data Without Electric Heat
Size (Tons)
Heater Circuit without units
Model KW Stages Amps
MCA
(Amps)
Max Fuse
Breaker
Size
(Amps)*
36 (3.0)
EHK-05J-15 3.8/5 1 18.1/20.8 23/26 25/30
EHK-08J-15 5.6/7.5 1 27.1/31.3 34/40 35/40
EHK-10J-15 7.5/10 1 36.1/41.7 46/53 50/60
EHK-15J-15 11.3/15 2 54.2/62.5 68/79 70/80
60 (5.0)
EHK-05J-15 3.8/5 1 18.1/20.8 23/26 25/30
EHK-08J-15 5.6/7.5 1 27.1/31.3 34/40 35/40
EHK-10J-15 7.5/10 1 36.1/41.7 46/53 50/60
EHK-15J-15 11.3/15 2 54.2/62.5 68/79 70/80
EHK-20J-15 15/20 2 72.2/83.3 91/105 100/110
Table 13 Electrical Data With Electric Heat
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per Standard UL 1995.
3. Fuse or HACR circuit breaker size fi eld installed.
* Max Fuse/Breaker Sizes are for electric heater ONLY (dual point electric heat).
DOES NOT include breaker size for the unit.
Refer to Electric Heat Kit Installation Manual, some heater kits
include fuses from the manufacturer.
WARNING: ELECTRICAL SHOCK / FIRE HAZARD
Any power supply and circuits must be wired and
protected in accordance with federal, state and local
electrical codes.