30
|
Installation Instructions
Bosch 15 SEER2 Inverter Ducted Packaged Heat Pump - BTC 761701319 A (12.2022)
13.8 Parameter Point Check Table
To display system parameters, press the “Check” button to
index through the series of parameters available. The first time
you press the “Check” button, it will display the sequence,
and after 1 second it will display the value of the parameter.
If you press the “Check” button again, it will display the next
sequence. Refer to Figure 32 for check button location on the
control board.
Figure 30
SW2
CHECK
No. Point check content Example Remark
0 Outdoor unit capacity RH5 RH5=Heat pump 5 ton
1 Outdoor unit mode 2
0 Standby,
2 cooling,
3 Heating
2 Outdoor unit set compressor speed(Hz) 66 66 Hz
3 T3(outdoor coil temp.) °F 108 108 °F
4 T4 (outdoor ambient temp.) (°F ) 95 95 °F
5 T5 (compressor discharge temp.) (°F ) 140 140 °F
6 T6 (compressor suction temp.) (°F ) 55 55 °F
7 T7(liquid line temp.) °F 99 99 °F
8 Tf (module temp.) (°F ) 120 120 °F
9 Pe (evaporating pressure) (PSI) 140 140 psi
10 Pc (condensing pressure) (PSI) 380 380 psi
11 Tes target of the evaporating temp. (only use for cooling mode) (°F ) 43 43 °F
12 Te (evaporating temp.) (°F ) 43 43 °F
13 Tcs target of the condensing temp. (only use for heatling mode) (°F ) 106 106 °F
14 Tc (condensing temp.) (°F ) 106 106 °F
15 Target of the compressor discharge superheat (only use for heating mode) (°F ) 36 36 °F
16 Compressor discharge superheat (°F ) 36 36 °F
17 Opening of EEV 200 200 p(0~480)
18 Fan speed 9 9 speed
19 Compressor current (A) 10 10 A
20 Alternating voltage 230 230 V
21 Compressor input dc voltage 380 380 V
22 Continuous running time of the compressor 35 35 min
23 Last Fault Code 00 see table 9-4 (*UPDATE*)
24 Software version 01 V1.0
25 T1 (Return air temp) (°F ) 70 70°F
26 T2 (Indoor coil temp) (°F ) 50 50°F
27 Indoor blower motor speed 4 4 speed
28 Ts (Estimated thermostat set point) (°F ) 70 70°F
29 Remark“--” -- --
Table 22
Normal Status, last two digits will display under the following
conditions
i. Unit not operating (Standby Mode); “outdoor ambient
temperature”.
ii. Unit operating; displays “compressor operating frequency”.
After 20 seconds on same parameter, the display will revert
back to normal status.
If a system protection is active, first digit will display “status
code”.