Bosch 15 SEER2 Inverter Ducted Packaged Heat Pump - BTC 761701319 A (12.2022)
13.11 Error Code Troubleshooting (IDU)
Number of fl ashes Description (Sensor)
4 Temperature sensor fault (T1)
5 Temperature sensor fault (T2)
Table 34
Figure 55
4/5 Flashes (Temperature sensor fault)
Diagnosis
Handling
Check whether T1/T2 sensor
is seated normally
Yes
Unplug the sensor and
measure the resistance to
ensure it's neither 0 nor ∞
No
Restart the unit to check if
the problem is resolved
Reseat sensors
No
Yes
Finish
Yes
No
Replace indoor control board
Replace sensors
Number of fl ashes Description (Sensor)
6 Communication error
Table 35
Figure 56
6 Flashes (Communication error)
Diagnosis
Handling
Check if the communication
wire is connected properly
(Refer to Figure 32 and 33)
Yes
Check if ODU control board
LED display is working
Yes
Restart the system
Correct the wire connections
No
No
Check if there is 230V
power input, if yes, replace
ODU board