16
|
Installation Instructions
Bosch 15 SEER2 Inverter Ducted Packaged Heat Pump - BTC 761701319 A (12.2022)
5 Air ow Performance
Airfl ow performance data is based on cooling performance with a coil and
no fi lter in place. Check the performance table (Table 6) for appropriate
unit size selection.
External static pressure should stay within the minimum and maximum
limits shown in the table below in order to ensure proper operation of
both cooling, heating, and electric heating operation.
Model
Number
Motor Speed *
SCFM
External Static Pressure-Inches W.C.[kPa]
0[0]
0.1[.02] 0.2[. 05] 0.3[.07] 0.4[.10] 0.5[.12] 0.6[.15] 0.7[.17] 0.8[.20]
36
Tap1
SCFM 1046
951 890 876 841 / / / /
Watts 110 120 131 135 143 / / / /
Amps 1.26
1.33 1.49
1.43 1.33 / / / /
Tap2
SCFM 1122
1075 1023
1009 976 931 / / /
Watts 148 158 170 174 183 196 / / /
Amps 1.52 1.6 1.68
1.71 1.77
1.87 / / /
Tap3
SCFM 1327 1287 1243
1229 1199
1158 1118 / /
Watts 234 247 260 265 275 290 306 / /
Amps
2.15 2.25
2.34 2.38 2.45
2.57 2.69
//
Tap4
SCFM
1411 1372
1330 1316 1285
1245 1206
1131 /
Watts 275 288 302 307 316 333 349 380 /
Amps
2.45 2.55
2.66 2.69 2.77 2.89
3.01
3.24 /
Tap 5
SCFM 1572 1538
1500
1487 1458 1419
1382
1353 1314
Watts 380 396 411 416 427 444 463 476 497
Amps 3.2 3.36 3.47 3.51 3.59 3.72
3.86 3.96 4.12
60
Tap1
SCFM 1398 1338 1282 1231 1175 /
///
Watts 166 176 187 198 208 / / / /
Amps 1.7 1.7 1.8 1.9 1.9 / / / /
Tap2
SCFM 1476 1420 1367 1316 1265 1213 / / /
Watts 194 205 217 228 239 250 / / /
Amps
1.9 2 2
2.1 2.2 2.3
///
Tap3
SCFM
1777 1728 1680
1635 1592 1549
///
Watts 323 338 352 365 378 391 / / /
Amps 2.8 2.9 3 3.1 3.2
3.3
/
/
/
Tap4
SCFM 1937 1889 1842 1792 1758
1720
1670
1636
/
Watts 412 428 444 457 471 486 499 513 /
Amps 3.5 3.6
3.7
3.8 3.9 4 4.1
4.2 /
Tap 5
SCFM 2235 2191 2144 2091 2050 2010 1971
1936 1892
Watts 623 642 660 673 689 704 719 734 744
Amps 4.5 5.1
5.3 5.4 5.5 5.6 5.7 5.8 5.8
Table 7
Bold outlined areas represent air ow outside of the required 300-450
cfm/ton range.
1 Silent Mode --- low stage speed.
2 Factory Default --- low stage speed.
3 Silent Mode --- high stage speed. Or High Static Pressure Mode --- low stage speed.
4 Factory Default --- high stage speed.
5 High Static Pressure Mode --- high stage speed.
NOTES:
1. This table is only used to select the highest blower speed.
2. The rated airfl ow of systems without electric heater kits requires between
300 and 450 cubic feet of air per minute (CFM).The rated airfl ow of
systems with electric heater kits requires between 350 and 450 cubic feet
of air per minute (CFM).
3. The air distribution system has the greatest eff ect on airfl ow. Therefore, the
contractor should use only industry-recognized procedures.
4. Duct design and construction should be carefully done. System
performance can be lowered dramatically through poor design or
workmanship.
5. Air supplier ducts should be located along the perimeter of the conditioned
space and properly sized. Improper location or insuffi cient air fl ow may
cause drafts or noise in the ductwork.
6. Installers should balance the air distribution system to ensure proper quiet
airfl ow to all rooms in the home. An air velocity meter or airfl ow hood can be
used to balance and verify branch and system airfl ow (CFM).
7. Factory Default maximum static pressure 0.6 inches W.C.. If static pressure
exceeds 0.6 inches W.C. please dial code to Tap(5)
For instructions on how to select fan speeds, refer to Section 6
of this manual.