Bosch AMAX panel 4000 - Output Programming

Bosch AMAX panel 4000
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
64 0804 - 0805 00 0869 1 0933 15
Value Range: 00 = zone
not used, 1 - 16 = Area 1-
16
Value Range:0–15. See
Section Zone Functions.
0 = On-board zone
1 = Keypad Zone
2 = DX2010 Zone *
3 = RF Device
15 = not used
* See next table
Notice!
When a zone is assigned to RF Device (3), then the dedicated zone on DX2010 is not
available.
Module Address
DX2010 module 1 (zones 17 - 24) 103
DX2010 module 2 (zones 25 - 32) 104
DX2010 module 3 (zones 33 - 40) 105
DX2010 module 4 (zones 41 - 48) 106
DX2010 module 5 (zones 49 - 56) 107
DX2010 module 6 (zones 57 - 64) 108
Output Programming
On-board Output Programming
Option Address Default
Keypad Alarm Tone, 0 = Disabled, 1 = Enabled 0503 1
Siren Running Time, 00 - 99 = 0 - 99 minutes 0508 - 0509 00
See The Value Ranges of Output Programming Options
Output 1 Output Event Type 0510 - 0511 05
VDS-A
EN=5
Output Area / Zone 0512 - 0513 00
Output Mode 0514 0
VDS-A EN=0
Output Time 0515 - 0517 180
VDS-A
EN=180
Output 2 Output Event Type 0518 - 0519 05
VDS-A
EN=5
Output Area / Zone 0520 - 0521 00
Output Mode 0522 0
VDS-A EN=0
Output Time 0523 - 525 000
VDS-A
EN=180
9.3
124 en | Programming
AMAX panel 4000 / AMAX panel 4000
EN
2013.07 | 03 | F.01U.267.112 Installation Guide Bosch Sicherheitsysteme GmbH