Figure 4.13: Wet mode and dry mode of the AMC2 relay outputs
Notice!
Risk of damage to equipment
To prevent damage to the relays note the following
specifications.
– the maximum switching current is 1.25 A
– the maximum switching voltage is 30 Vdc
– only ohm resistive load can be connected to the relay
– inductive loads have to be short circuited using recovery
diodes, see image below. These diodes (1N4004) are
supplied with every AMC2-4WE package.
– If you need higher voltage for special applications you can
connect external relays to the outputs. Recommended,
depending on the power supply mode, are the relay types
from the Wieland company:
– Flare move 12DC1W10A
– Flare move 24DC1W16A
If using locally manufactured products, please ensure that the
specifications of the product are identical with the those listed
above.