AVENAR panel 8000 | AVENAR panel 2000 |
AVENAR keypad 8000
Further functions | pt-BR 87
Bosch Sicherheitssysteme GmbH
Manual do utilizador
2023-08 | 8.0 | F.01U.378.877
Fire alarm Fault/ supervisory alarm
Display switches to Alarm indication Fault indication
Fire drill after event ends Must be restarted
manually
Continue
A new function cannot be selected until the fault/supervisory alarm and/or the fire drill have
been completed.
20.7 Alarm Counters
Show Lifetime Event Counters
During the lifetime of the panel, the following alarm conditions and messages are counted
locally for each panel (Local) and in scope for all panels within the complete network or a
network group, depending on the configuration (Âmbito):
– External alarm: all fire alarm conditions which triggered an external device
– Internal alarm: all fire alarm conditions which did not trigger an external device (e.g. if the
alarm occurred in daymode)
– Maintenance alarm: all alarm messages from detectors in walktest mode.
To display the number of alarm conditions and messages which have been counted so far:
1. In the start menu, select Outras funções
2. Contadores de alarmes
The figure after the message type shows the number of conditions and messages counted so
far for the individual panel (Local) and summed up for all panels in the complete network or a
network group, depending on the configuration (Âmbito).
Aviso!
O âmbito dos contadores depende da configuração do Âmbito do nó no software de
programação FSP-5000-RPS. Se Grupo for definido, são contados os alarmes e as condições
de todos os painéis num determinado grupo de redes, dependendo do endereço de nó lógico.
Se Rede for definido, são contados todos os alarmes e condições de todos os painéis na
rede.
Reset counters
You can reset the alarm counter for individual alarm types to 0.
To reset alarm counters
1. In the start menu, select Outras funções
2. Contadores de alarmes
3. Mark the alarm counter you require (e.g. external alarm)
4. Select Reset
5. Confirm the message "Atenção: O contador vai ser reposto" with OK to reset the alarm
counter to 0 or select Cancelar to cancel the operation.
6. Reboot the panel to display the reset values.
Aviso!
In order to reset alarm counters, you need authorization level 4.