10 en | Test procedure AVIOTEC 8000i IR
2023-10 | 01 | F.01U.414.170
Commissioning
Bosch Sicherheitssysteme GmbH
4.2 Smoke detection (test video)
Figure4.3: Test setup (smoke detection, test video)
1. Place a playback device (computer monitor or a tablet computer) in the detection area
in front of the camera.
2. Align the monitor to the test camera.
3. Play the video for smoke detection.
ð A smoke alarm shall be triggered within the set smoke verification time plus 15 s. A
connected video client shall show a rectangular box around the smoke region.
Enter the results in the commissioning report.