AVIOTEC 8000i IR Test procedure | en 11
Bosch Sicherheitssysteme GmbH
Commissioning
2023-10 | 01 | F.01U.414.170
4.3 Flame detection (test video)
Figure4.4: Test setup (flame detection, test video)
1. Place a playback device (computer monitor or a tablet computer) in the detection area
in front of the camera.
2. Align the monitor to the test camera.
3. Play the video for flame detection.
ð A flame alarm shall be triggered within the set flame verification time plus 15 s. A
connected video client shall show a rectangular box around the flame region.
Enter the results in the commissioning report.