Modular configuration units
CS3000 AWP – 6721852570 (2023/04)
70
14 Modular configuration units
This feature allows up to 16 units to be connected.
The system is completely controlled by the Master unit. Each connected
module is identified by an address, from 0 to 15: the Master unit is
identified as 0.
The TW leaving water temperature control probe, the flow switch and the
auxiliary electric heater must be controlled by the master unit.
All units must be electrically connected to each other via the X-Y-E BUS.
Each module can be equipped with an inertial system storage tank.
Each unit with DHW option must have its own DHW storage.
An external pumping unit sized for the entire capacity of the modular
system must be provided (by the Customer). The pumping unit will be
managed by the Master unit through a potential-free contact and 0-10V
signal.
The TW probe of the master unit must be reinstalled on the common
supply line from all units, as far away as possible.
Fig. 98 Communication modular unit
Fig. 99 TW probe
Fig. 100 System diagram with inverted return connection
Table 60 Example dimensions for a standard system
0010045043-001
Cooling (Kw)
Water pipe
Min Max IN/OUT
15 30 DN40
30 90 DN50
90 130 DN65
130 210 DN80
210 325 DN100
325 510 DN125
510 740 DN150
740 1300 DN200
1300 2080 DN250
Slave Slave Master
Tw
Adr.2 Adr.1 Adr.0
0010045044-001
Addr = 15
ACS ACS
MAX 16 UNIT
MAX 4 UNIT
MAX 4 UNIT
MAX 4 UNIT
MAX 4 UNIT
ACS
Addr = 1
ACS
Addr = 0
SLAVE SLAVE MASTER
0010045045-001