79
CS3000 AWP – 6721852570 (2023/04)
16.4 Dimensional drawings
AWP16, AWP19, AWP24
[1] Compressor enclosure
[2] Electrical panel
[3] Power input
[4] Inlet water connection 1” 1/2 victaulic
[5] Outlet water connection 1” 1/2 victaulic
[6] Functional spaces
[7] Electrical fan
[8] Unit fixing holes
[9] External exchanger
[10] DHW inlet (optional) 1 1/2” victaulic
[11] DHW outlet (optional) 1 1/2” victaulic
Table 74
Table 75 Weight distribution
1)Includes the water capacity of a standard heat pump without heating
pump.
2)Includes packaging materials and wooden pallet / Optional accessories
may result in a substantial variation of the weight in the table.
0010045735-003
1
6
6
6
7
W2
W4
W3
W1
2
9
3
8
10
4
11
5
8
272
205
205200
204
6000
800
800
800
800
1861
825518 419
1340
6
2
1920
1005
198
94424
24
SIZE AWP16 AWP19 AWP24
Lenght mm 1920 1920 1920
Depth mm 1005 1005 1005
Height mm 1340 1340 1340
Operating weight
1)
kg 323 323 323
Shipping weight
2)
kg 333 333 333
Series BT/ BU STD BT/ BU
Size AWP16 - AWP24 AWP16 - AWP24
Optional STD ACC+PUMP
W1 Support point kg 98 135
W2 Support point kg 78 118
W3 Support point kg 98 149
W4 Support point kg 78 132
Operation weight
1)
kg 323 534
Shipping weight
2)
kg 333 400