Questions and Answers

  • M
    Matthew CarterSep 7, 2025
    How to troubleshoot a Bosch LV060 with no compressor operation but running fan, possibly due to blocked return air?
    • C
      Christopher GarrisonSep 7, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a condensate fault caused by blocked return air. Check the condensate pan for a high water level. Also, check the air filter and return air duct work for blockage, and ensure there is adequate space between the return air opening and any obstructions.
  • T
    Trevor RodriguezAug 22, 2025
    Why is my Bosch Heat Pump not shifting into cooling?
    • E
      epageAug 22, 2025
      If your Bosch Heat Pump isn't shifting into cooling mode, check that the reversing valve solenoid is receiving 24 VAC. If it is, check the resistance of the solenoid; an open circuit may indicate a burned out solenoid. Also, check that the reversing valve thermostat wire is connected to the 'O' terminal of the thermostat and check for a contact closure between 'O' and 'R'. Finally, check that the wires from the thermostat to the unit are securely connected and that the wires from the electrical box to the reversing valve are connected.
  • A
    Amy JohnsonSep 4, 2025
    What to do if the compressor of my Bosch LV060 doesn't work but the fan runs and there is a freeze fault caused by low refrigerant?
    • A
      ariel78Sep 5, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a freeze fault in the air coil caused by low refrigerant. Check the refrigerant pressure with a gauge set.
  • A
    Angela ThomasSep 3, 2025
    How to troubleshoot a Bosch Heat Pump with no compressor operation but running fan, possibly due to a bad thermostat connection?
    • M
      Michael CabreraSep 3, 2025
      If the compressor of your Bosch Heat Pump is not working, but the fan is running, it might be due to a brown-out fault caused by a bad thermostat connection. Check that the thermostat wiring is of the proper gauge and length, is undamaged, and that all connections at the thermostat and heat pump are secure.
  • F
    Frances AndersonSep 2, 2025
    What to do if my Bosch LV060 Heat Pump compressor isn't running but the fan is on and I suspect an overloaded control circuit?
    • E
      Eric BassSep 2, 2025
      If the compressor of your Bosch Heat Pump is not working, but the fan is running, it might be due to a brown-out fault caused by an overloaded control circuit. Check the control voltage; if it's below 18V, inspect the accessories connected to the unit and ensure they don't exceed the VA draw.
  • R
    Raymond Johnson MDAug 31, 2025
    Why is my Bosch Heat Pump compressor not running but the fan is, possibly due to low airflow?
    • S
      Steve JonesAug 31, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a low-pressure fault caused by no or low airflow. Check the fan motor to ensure it is operating correctly.
  • B
    Brenda WestAug 30, 2025
    What to do if my Bosch LV060 Heat Pump compressor isn't running but the fan is, and I suspect airflow issues?
    • H
      henryconnieAug 30, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by no or low airflow. Check the fan motor to ensure it is operating correctly.
  • V
    Vincent JamesAug 29, 2025
    How to troubleshoot a Bosch LV060 Heat Pump with no compressor operation but running fan, possibly due to a fouled water coil?
    • M
      Michelle FieldsAug 29, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by a fouled or scaled water coil. Check for proper flow rate and water temperature, especially looking for a low water side temperature rise during cooling.
  • B
    Benjamin NealAug 27, 2025
    Why is my Bosch LV060 Heat Pump compressor not running but the fan is, possibly due to high water temperature?
    • T
      Tyler ScottAug 27, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by high water temperature. Check the water temperature to ensure it is within the appropriate range.
  • D
    denise67Aug 27, 2025
    What to do if the compressor of my Bosch Heat Pump doesn't work but the fan runs and there is a freeze fault?
    • J
      John PatelAug 27, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a freeze fault in the water coil caused by no or low water flow. Check the water valves and/or pumps to ensure they are operating correctly. Also, check the water coil for any blockages.

Summary

Key Symbols and Safety Warnings

Safety Warnings

Critical instructions for installation, servicing, and operation.

Installation - Site Preparation

Step 1- Check Job Site

Procedures for checking the job site before installation.

Step 2- Check Unit

Procedures for inspecting the unit upon receipt.

Installation - Unit Placement

Step 3- Locate the Unit

Instructions for locating the unit for optimal installation.

Installation - Mounting and Ducting

Step 4 Mount The Unit

Guidelines for mounting vertical and horizontal units.

Installation - System Connections

Step 5 Check Duct System

Procedures for checking and preparing the duct system.

Installation - Connections and Wiring

Step 7-Pipe Connections

Guidelines for making water piping connections.

Step 8 Wire Field Power Supply

Instructions for wiring field power supply to the unit.

Unit Controls and ECM Interface

ECM-UPM Controls

Description of the ECM-UPM unit controls and interface board.

Safety Features and Protection

Safety Features Overview

Details of the unit's integrated safety features.

Freeze Protection and Reset

Information on freeze sensors, intelligent reset, and lockout reset.

Pre-Start-Up and Start-Up Procedures

System Checkout

Essential checks before initial unit startup.

Unit Start-Up

Procedure to initiate proper unit startup.

Compressor Operation

Unit Start-Up Modes

Certified Performance Data

Fan Motor Options

Blower Motor Electrical Data

Troubleshooting Common Issues

Operating Data Tables

Waterside Pressure Drop Table

Compressor Characteristics

Unit Check Out Sheet

Bosch LV060 Specifications

General IconGeneral
BrandBosch
ModelLV060
CategoryHeat Pump
LanguageEnglish

Related product manuals