52 en | Best Practices for Outdoor Installation MIC IP ultra 7100i │ MIC IP starlight 7100i
2019-07-03 | 0.17 | Installation Manual Bosch Security Systems
1 Indoor main building 2 Network equipment
3 Connect the ground of the camera
power supply to the building earth
ground.
4 Surge protection
5 Connect the ground of the camera to
the ground of the surge protector.
6 Install Cat5e/Cat6 (Shielded Twisted
Pair (STP)) Ethernet cable. Route the
cable through grounded, metal
conduit.
Isolate high voltage power lines in a
separate conduit.
7 Equipment enclosure 8 Outdoor rated High PoE-compatible
midspan
9 Connect the Bus Bar to the Equipment
Grounding Electrode.
10 Outdoor High PoE-compatible surge
protection to protect indoor
equipment
11 Equipment Grounding Electrode 12 Lightning Rod
13 Down Conductor; refer to NFPA 780,
Class 1 and 2.
14 Install outdoor High PoE-compatible
surge protection as close as possible
to the camera. Connect to the
Equipment Grounding Electrode.
15 Lightning Rod Grounding Electrode