Bosch Security Systems | 2006-06 | 9922 141 10377 en
Plena Voice Alarm System | Installation and User Instructions | IEC60849 en | 117
IEC60849 - 5.10 Connectors
IEC60849 - 6. Installation requirements
table 15: IEC60849 - 5.10 Connectors
Requirement Compliance Signature
Connectors shall comply with IEC60268-11 or
IEC60268-12. Requirements for fire
resistance of connectors may also be
stipulated by the relevant authorities.
Connectors comply with IEC60268-11 or
IEC60268-12. Additional requirements are the
responsibility of the installer, i.e. cables wiring and
loudspeakers should comply with IEC60849.
Responsibility of the installer.
table 16: IEC60849 - 6. Installation requirements
Requirement Compliance Signature
The system shall be installed in accordance
with IEC60364 or with mandatory national or
local standards.
Responsibility of the installer.
If the emergency sound system forms part of
an emergency detection and/or alarm system,
the cabling shall meet the requirements of
mandatory national or local, emergency and/or
alarm system standards. Where the application
specifically excludes detection and/or alarm,
the cabling shall be of a standard suitable for
the application.
Responsibility of the installer.
Precautions shall be taken to prevent the
spread of hazardous effects via the wiring
routes.
Responsibility of the installer.
When a sound system for emergency
purposes is installed in combination with an
emergency detection system, the installation
standards for the sound system shall comply
as far as is applicable with the standards
required for that detection system.
Responsibility of the installer.
When additions and/or modifications are made
to a non-compliant system the existing system
may require to be upgraded to meet this
standard. In all cases the additions and/or
modifications shall meet this standard.
Responsibility of the installer.