4-16 ECODRIVE DKC drive controllers ECODRIVE DKC02.1 Drive Controller
DOK-ECODRV-DKC02.1****-PRJ2-EN-P
FP5106F5.fh5
ECODRIVE
3
2
1
ON
OFF
S4
Switch for transmission power settings
Switch for data rate settings
Fig. 4-20: Position of the switch for data rate and transmitter power demonstrat-
ing how to switch it ON and OFF.
The data rate is set with the switch S4/1.
Position of switch S4/1 Data rate in Mbit/s
OFF 2
ON 4
Fig. 4-21: Relationship between switch position S4/1 and the data rate
The transmitter power is set with the switches S4/2 and S4/3.
The following table demonstrates the relationship between switch position
and transmitter power.
Position of
switch S4/2
Position of
switch S4/3
Transmitter
power at an
opt. high level
in dBm
Transmitter
power at an
opt. high level
in µW
OFF OFF -7 200
OFF ON -4,5 350
ON OFF -1 800
ON ON 0 1000
Fig. 4-22: Relationship between switch position S4/2, S4/3 and the
Data rate
Transmitter power
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01