ECODRIVE DKC02.1 Drive Controller ECODRIVE DKC drive controllers 4-11
DOK-ECODRV-DKC02.1****-PRJ2-EN-P
X4 24V control voltage supply, E-stop (emergency stop), stand-by
operation
Maximum wire cross section which can be connected: 2.5 mm
2
Voltage at X4/1: DC +24 V (± 20%)
Current consumption X4/1: 0.6 A
An error message is displayed if there is a 20% drop in the 24 V.
Note: If the 24 V control voltage fails, the motor will coast torque-free
(unbraked).
DANGER
Dangerous movements!
Danger may result in equipment damage, personal injury
or death!
Keep clear of the machine's movement area. Possible
measures to be taken to prevent access by unauthor-
ized persons:
- protective fence
- protective railing
- protective covering
- light barrier
Fences and coverings should be strong enough to
withstand the maximum possible momentum.
The E-stop input can be used as a second, redundant shutdown input. It
serves to trigger a shutdown independent of NC and SERCOS.
Requirement:
The E-stop input is available if the E-stop function in the software is acti-
vated (see function description).
If no voltage is applied to the E-stop input, the error response will be exe-
cuted which can be set in the drive controller.
The SERCOS interface offers all the options necessary for reliable opera-
tion. Even a complete communication failure between the control and
drive has been taken into account and results in a defined error response.
For applications
in which communication failures between the NC part of the control
and the SERCOS master module have to be stored (see
1
)
in which the connected SPS does not sufficiently monitor the E-stop
circuit and thus does not trigger a drive response in time (see
2
)
it is necessary to obtain an error response from the drive as fast as pos-
sible.
24 control voltage supply
E-Stop
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01