EasyManua.ls Logo

Bosch Solution 64 - Page 72

Bosch Solution 64
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Solution 64
|
Installer Guide
|
Comms Programming
9-10
Bosch Security Systems | 11/05 | BLCC110I
Comms > Dialler Reporting >
TX Format Dest 2
MENU 5-4-1
0 = Disable 1
1 = Contact ID 7 = Domestic
2 = SIA 8 = Voice 13 = Reserved
3 = Serial STU 9 = Panel 1 (Node 1) 14 = Reserved
4 = GSM 10 = Panel 2 (Node 2) 15 = Reserved
5 = WEB MAIL 11 = Panel 3 (Node 3)
6 = SMS 12 = Panel 4 (Node 4)
This menu allows you to program the transmission format
or language the panel will use to send event reports to
Destination 2.
Press [MENU] + [5] + [4] + [1]. The keypad will display the
current Transmission Format for Destination 2.
TX Format Dest 2 N001
01-Contact ID
Press 0-9 OK to SAVE
Use the up and down arrow keys to select the Transmission
Format required then Press [OK] to save and exit or press
[MENU] to exit without saving.
i
Note
Transmission Formats 9 -12 are not applicable on the Solution
64 control panel and should not be programmed. Other
formats may require additional hardware or add on modules to
function.
Comms > Dialler Reporting
Test Route
MENU 5-4-2
0 = Report Events To Log Only 1
1 = Report Events To Destination 1 + Log
2 = Report Events To Destination 2 + Log
3 = Report Events To Destination 1 & Destination 2 + Log
4 = Report Events To Destination 2 If Destination 1 Fails + Log
This menu programs which destination will be used to send
both manual and automatic test reports.
(*** System Wide Parameter ***)
Press [MENU] + [5] + [4] + [2]. The keypad will display the
current Test Route.
Test Route
01-Dest 1 + Log
Press 0-9 OK to SAVE
Use the up and down arrow keys to select the Test Route
required then Press [OK] to save and exit or press [MENU] to
exit without saving.
1)
2)
1)
2)
Comms > Dialler Reporting
Status Route
MENU 5-4-3
0 = Report Events To Log Only 1
1 = Report Events To Destination 1 + Log
2 = Report Events To Destination 2 + Log
3 = Report Events To Destination 1 & Destination 2 + Log
4 = Report Events To Destination 2 If Destination 1 Fails + Log
This menu sets the report destination that will be used to send
all system event reports.
(*** System Wide Parameter ***)
Press [MENU] + [5] + [4] + [3]. The keypad will display the
current Status Report route.
Status Route
01-Dest 1 + Log
Press 0-9 OK to SAVE
Use the up and down arrow keys to select the Test Route
required then Press [OK] to save and exit or press [MENU] to
exit without saving.
Comms > Dialler Reporting
Emergency Route
MENU 5-4-4
0 = Report Events To Log Only 1
1 = Report Events To Destination 1 + Log
2 = Report Events To Destination 2 + Log
3 = Report Events To Destination 1 & Destination 2 + Log
4 = Report Events To Destination 2 If Destination 1 Fails + Log
This menu programs the destination that all Keypad
emergency alarms are reported.
(*** System Wide Parameter ***)
Press [MENU] + [5] + [4] + [4]. The keypad will display the
current Emergency Route.
Emergency Route
01-Dest 1 + Log
Press 0-9 OK to SAVE
Use the up and down arrow keys to select the Keypad
Emergency route required then Press [OK] to save and exit or
press [MENU] to exit without saving.
1)
2)
1)
2)

Table of Contents