Commissioning
Greenstar Danesmoor External
ErP+
and External System
ErP+
6720821725 (2018/04)30
▶ Turn on the boiler, set the programmer to ON and turn the room
thermostat up to create a demand for heat.
The oil level in the de-aerator will drop whilst the oil is being drawn
from the tank. If the de-aerator empties and the burner locks out
before the oil is drawn from the tank, you will have to prime the de-
aerator again.
Fig. 48 Prime the oil supply pipework
[1] Oil supply
[2] De-aerator
[3] Return
[4] Flow
[5] Spare flexible oil hose
[6] Container of oil
[7] Oil pump flexible inlet hose
[8] Bleed and pressure gauge port
▶ Switch off the boiler.
▶ Safely dispose of the container/discharge.
6.4.3 Pump adjustments
2. Fit a suitable pressure gauge to port [3] on the oil pump.
Fig. 49 Oil pump ports/connections
[1] Vacuum gauge port
[2] Pressure adjuster
[3] Bleed and pressure gauge port
[4] Return connection
[5] Inlet connection
[6] Auxiliary pressure gauge port
▶ Adjust the air shutter [3] figure 50 and pump pressure [2]
figure 49 as shown in the table 9 on page 32. The burner should
ignite following a pre-ignition period of approximately 15 seconds.
▶ If changing the burner output, check the position of the air damper
disc is correct to the output as shown in the table below.
Fig. 50
[1] Lockout reset button
[2] Blast tube
[3] Air shutter adjuster
[4] Captive screws air intake cover
[5] Air damper disk
6.4.4 Burner head setting
Adjustments to the burner head are made on the basis of the required
output, refer to table 9 for the required setting for your boiler.
Fig. 51 Burner head adjustment thumbwheel
One complete rotation clockwise (cw) from the minimum position
equals approximately one millimetre. Adjust the thumb-wheel to achieve
the setting indicated in the table 9, according to your appliance model
and output.
Using an engineer’s rule or vernier gauge measure from the lip of the
blast tube to the inside of the break plate as show in the figure below.
Ensure that the break plate is level, check at four equal points to get an
average of the required setting. The setting tolerance should be no more
than ± 0.25mm
Adjust position of air damper discs to suit burner output
(see table 9 on page 32), located as above. Access by
undoing the two screws [4] to release the air inlet cover.
3
4
2
5
7 3
1
6
6720813288-04.1Wo
8