Service and Spares
Greenstar Danesmoor External
ErP+
and External System
ErP+
6720821725 (2018/04)34
7 Service and Spares
7.1 Inspection and service - 18/25 Regular shown
Routine servicing
To maintain efficient boiler operation, the following should be carried
out at least once a year, carry out a pre-service check and note any
operational faults.
Service requirements
See the following instructions for detail of some of the service
requirements:
Check that the safety and regulation devices (3 bar safety valve, air
bleed, etc.) are operating properly.
Also check that neither the installation nor the appliance present any
water or fuel leaks, (leaks may produce a safety risk and shorten the
life-span).
Clean or replace all oil filters.
When it is frequently necessary to add water to maintain pressure in
the installation, even though no leaks have been discovered, perform
an expansion vessel check.
Check that the condensate system is not obstructed, clean and refill
the condensate trap as necessary.
Check the condition of the various seals (burner flange, burner door,
flue outlet, etc.).
Check and clean the burner.
Replace the burner nozzle and flexible oil pipe/s.
Check and clean the primary and secondary baffles.
Check and clean the heat exchangers surfaces.
Check the combustion chamber access door insulation board.
Check that the flue system is unobstructed and clean as necessary.
Sealed system only
The PRV is a safety device and must be checked for correct operation.
The expansion vessel pressure must also be checked and adjusted if
required.
Oil supply system and tank
The oil pipeline, filters, fire valve and tank should be inspected and
maintained in accordance with OFTEC regulations.
Fire valve
Check that the oil supply pipe has a fire valve fitted externally to the
building with the fire valve sensor located within the appliance case.
A fire valve sensor clip is provided for this purpose on the support bar
between the side panels.
The fire valve should be rated at 85 °C or above to avoid nuisance cut
outs.
Pre-service checks
Release the latches [3] at the base of the front panel [2] using the
key provided and lift the panel and pull towards you to remove. Store
the panel safely away from the working area.
Operate the appliance and system and note any faults which may
need to be corrected during the service.
Switch into service mode at switch [1].
Fig. 58 Access to internal components
Unplug burner lead [1]from control box.
Unscrew to loosen the retaining ring [4] that secures the flexible air
supply tube [3] to the burner and remove from the burner.
Undo and remove the retaining nut [2] on the top of the burner.The
burner can now be removed from the heat exchanger. Store the
burner and retainer nut safely away from the boiler.
Fig. 59 Disconnecting burner
CAUTION: MAINS SUPPLIES
Isolate the water, electricity, and oil mains supplies
before starting any work and observe all relevant
safety precautions.
6720809437-37.2Wo
2
1
3
6720809437-16.1Wo
2
4
3
1