EasyManua.ls Logo

Bryant 580D - PHYSICAL DATA - 580 D036-072 (cont)

Bryant 580D
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PHYSICAL DATA 580D036-072 (cont)
UNIT SIZE 580D
036
MEDIUM/
HIGH HEAT
048
LOW/MEDIUM/
HIGH HEAT
060
LOW/MEDIUM/
HIGH HEAT
072
LOW/MEDIUM/
HIGH HEAT
FURNACE SECTION
Rollout Switch Cutout
Temp (F)** 195 195 195 195
Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std .113...33 .113...33/.113...33/.129...30 .113...33/.113...33/.129...30 .113...33/.113...33/.129...30
Liquid Propane Alt .089...43 .089...43/.089...43/.102...38 .089...43/.089...43/.102...38 .089...43/.089...43/.102...38
Pilot Orifice Diameter
(Quantity) in. ...drill size
Natural Gas Std ———
Liquid Propane Alt ———
Thermostat Heat Anticipator
Setting (amps)
208/230 v and 575 v Stage 1 .14 .14 .14 .14
Stage 2 .14 .14 .14 .14
460 v Stage 1 .14 .14 .14 .14
Stage 2 .14 .14 .14 .14
Gas Input (Btuh) Stage 1 72,000/82,000 72,000/115,000/120,000 72,000/115,000/120,000 72,000/115,000/120,000
Stage 2 —/115,000 —/—/150,000 —/—/150,000 —/—/150,000
Efficiency (Steady
State) (%) 80 80 80 80
Temperature Rise Range 25-55/55-85 25-55/35-65/50-80 25-55/35-65/50-80 25-55/35-65/50-80
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5
Liquid Propane Alt 3.5 3.5 3.5 3.5
Gas Valve Quantity 1111
Gas Valve Pressure Range
Psig 0.180-0.487 0.180-0.487 0.180-0.487 0.180-0.487
in. wg 5.0-13.5 5.0-13.5 5.0-13.5 5.0-13.5
Field Gas Connection
Size (in.)
1
2
1
2
1
2
1
2
HIGH-PRESSURE SWITCH (psig)††
Standard Compressor
Internal Relief (Differential)
450±50 500±50
Cutout 428 428
Reset (Auto.) 320 320
LOW-PRESSURE SWITCH (psig)††
Cutout 7±3
Reset (Auto.) 22±7
FREEZE PROTECTION
THERMOSTAT (F)**
Opens 30±5
Closes 45±5
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.) 1...20 x 24 x 1
RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 2...16 x 25 x 2
LEGEND
Al Aluminum
Bhp Brake Horsepower
Cu Copper
*Evaporator coil fin material/condenser coil fin material. Contact your
local representative for details about coated fins.
†Weight of 14-in. roof curb.
**Rollout switch lockout is manually reset by interrupting power to unit
or resetting thermostat.
††Requires an optional or accessory Controls Upgrade Kit.
NOTE: The 580D036-150 units have a loss-of-charge/low-pressure
switch (accessory or option) located in the liquid line.
9