EasyManuals Logo

Bryant 582J Series Installation Instructions

Bryant 582J Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
19
Disconnect
per
NEC
Disconnect
per
NEC
208/230-1-60
11 13 11 13 13
L1
L2 L3
TB
C
C IFC
or
(1-ph
IFM)
208/230-3-60
460-3-60
575-3-60
Units Without Non-Fused Disconnect Option
Units With Non-Fused Disconnect Option
2
4
6
1
3
5
L1
L2
L3
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
C14241
Fig. 24 -- Power Wiring Connections
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in
intermittent operation or perfor mance satisfactio n.
Do not connect aluminum wire between disconnect
switch and 582J unit. Use only copper wire.
(See Fig. 25.)
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
A93033
Fig. 25 -- Disconnect Switch and Unit
Units with Factory--Installed Non--Fused Disconnect
The factory--installed option non--fused disconnect (NFD)
switch is located in a weatherproof enclosure located
under the main control box. The manual switch handle and
shaft are shipped in the disconnect enclosure. Assemble the
shaft and handle to the switch at this point. Discard the
factory test leads (see Fig. 24).
Connect fiel d power supply conductors to LINE side
terminals when the switch enclosure cover is removed to
attach the handle.
C12278
Fig. 26 -- Location of Non--Fused Disconnect Enclosure
To field install the NFD shaft and handle:
1. Remove the unit front pane (see Fig. 2).
2. Remove (3) hex screws on the NFD enclosure -- (2) on
the face of the cover and (1) on the left side cover.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from t he factory is at
OFF position (the arrow on the black handle knob is
at OFF).
5. Insert the shaft with the cross pin on the top of the shaft
in the horizontal position.
6. Measure from the tip of the shaft t o the top surface of
the black pointer; the measurement should be 3.75 --
3.88 in. (95 -- 99 mm).
7. Tighten the locking screw to secure the shaft to the
NFD.
8. Turn the handle to the OFF position with red arrow
pointing at OFF.
9. Install the handle on to the painted cover horizontally
with the red arrow pointing to the left.
10. Secure the handle to the painted cove r with (2) screws
and lock washers supplied.
11. Engaging the shaft into the handle socket, re--install
(3) hex screws on the NFD enclosure.
12. Re--install the unit front panel.
C12279
Fig. 27 -- Handle and Shaft Assembly for NFD
582J

Table of Contents

Other manuals for Bryant 582J Series