3.4 Configuring the CAN Bus Interface
3.4.1 Configuring the Connector Socket X101 for Networking
The connector socket X101 must be configured as external CAN
bus for networking in order to enable data exchange via the CAN
bus interface of the ekr 500 digital Unit Touch controller. Config-
uration is made using DIL switch S5 on the processor board of the
controller.
Fig.8: DIL switch S5 on the processor board of the controller
Procedure
NOTICE
Damage to the components from working on live parts.
►
Before opening the controller, switch off the power supply.
1. Electrically isolate the controller.
2. Open the controller’s housing cover.
3. Set DIL switch S5.6 on the processor board of the controller to
position ON.
4. Close the controller’s housing cover.
5. Switch on the power supply of the controller again.
Changes to the DIL switch settings will become active
only after a restart of the controller.