Buderus Logamax plus GB162-100 kW - Check and Adjust the Gas;Air Ratio

Buderus Logamax plus GB162-100 kW
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9
Start-up procedure
Logamax plus GB162- 80/100 kW - Subject to modifications resulting from technical improvements!
43
Measure the gas supply pressure and enter it in the
start-up report. Æ paragraph 15.1 "Start-up report",
page 67.
To obtain the best preformance of the appliance, the gas
supply pressure must be:
Press the “Service” e button (fig. 62, [4]) repeatedly
until the temperature reading is shown in the display.
Press the “Chimney sweep” d button (fig. 62, [3]) to
clear the reading. Æ table 12, "Flue gas test",
page 35.
Fig. 62 BC10 basic controller
1 Main switch
2 “Reset” button
3 “Chimney sweep” button
4 “Service” button
5 Connection possibility for the diagnosis connector
6 LED “Burner operation”
7 LED “Central heat demand
8 Space heating water temperature knob
9 Display
10 DHW temperature knob
11 LED “DHW demand”
Close the gas valve.
Remove the gauge-connection tube and tighten the
screw plug on the testing nipple again.
Open the gas valve again by pushing on the gas valve
and turning it ¼ rotation in a counterclockwise
direction.
9.8 Check and adjust the gas/air ratio
Open at least 2 thermostatic radiator valves, if present.
Do not switch ON the boiler.
Push on the control panel to open it.
Switch OFF the heating system by pressing the main
switch of the BC10 basic controller (fig. 62, [1]).
Close the gas valve (fig. 60).
Turn the vent key through a ¼ rotation to undo the
boiler door lock (fig. 51, see detailed picture).
Gas supply
pressure
Natural gas
inch W.C.
(mbar)
LPG inch
W.C.(mbar)
Min. 7 (17.4) 8 (19.9)
Nom. 8 (19.9) 11 (27.4)
Max. 10,5 (26.1) 13 (32.3)
Tab. 17 Gas supply pressure
WARNING:
A leaking testing nipple causes explosive
fumes.
B Check the testing nipples used for leaks.
B Only use approved detection products to
locate leaks.
1
123456
11
10 9 8
7
110
140
130
120
90
100
130
170
150
90
110
190
6720645916-47.1N
NOTICE
B If the supply pressure is too low, check the
gas supply pipe or contact the relevant
gas utility company if the required supply
pressure is not available.
B If the supply pressure is too high, a gas
pressure regulator must be integrated
upstream of the gas fitting. Contact the
gas utility company.
WARNING:
Damage to the boiler by incorrect adjustment
of the gas/air ratio.
B Adjust gas/air ratio ONLY with part load!
B Adjust gas/air ratio ONLY based on the
gas/air pressure differential and never
based on measured flue gas values such
as CO/CO
2
/NOX!
WARNING:
A leaking testing nipple causes explosive
fumes.
B Check the testing nipples used for gas
tightness.
B Only use approved detection products to
locate leaks.
CAUTION:
Due to short circuits.
B Cover any hazardous locations prior to
locating the leaks.
B Do not spray the leak detection product
on cable runs, plugs or electrical wiring.
Do not let it drip onto them either.