13
System inspection and maintenance
Logano G515 – 6 720 647 208 (2014/09) 41
13.4 Wet-cleaning the boiler
When wet-cleaning, pick the cleaning agent based on the level of
contamination.
Proceed with wet cleaning in the same order as described for cleaning
with cleaning brushes ( Chapter 13.3, page 39).
Select a cleaning agent that is appropriate for the type of
contamination (soot or encrustation).
Cover the control panel with foil to prevent penetration by the
cleaning agent.
Spray cleaning agent evenly from the top into the flue gas passages
Heat up the boiler to a boiler water temperature of at least 158 °F
(70 °C).
Brush out the heat exchanger heater.
13.5 Checking the operating pressure
The operating pressure must be at least 15 psi (1 bar).
Read the current operating pressure (psi) and temperature (°F (°C))
from the temperature/pressure gauge.
If the operating pressure drops below 15 psi (1 bar), fill boiler water.
Fig. 77 Pressure/temperature gauge
13.6 Filling with boiler water and purging the system
Slowly fill the heating system via the on-site fill valve. During filling,
observe the display (pressure gauge).
Once the desired operating pressure is reached, stop the procedure.
Purge the air from the heating system via the purge valves on the
heating bodies.
Fill with water again if the operating pressure drops as a result of
purging the system.
For wet-cleaning (chemical cleaning), observe the
operating instructions of the relevant cleaning
equipment and cleaning agent. It may be necessary to
vary the wet-cleaning process from that described here.
7 747 019 141-17.1RS
NOTICE: Risk of system damage from temperature
stresses.
When the heating system is in operation, do not fill it
via the boiler fill & drain valve. Instead, use the fill
valve on the system side.
Bring the system up to the required operating pressure.
NOTICE: Risk of system damage from frequent refilling.
The system may be damaged, depending on water
quality, by corrosion or scaling, if you frequently
need to re-fill your system with make-up water.
Ensure that your heating system is bled.
Check the heating system for leaks and the function
of the expansion vessel.

Table of Contents

Other manuals for Buderus Logano G515

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logano G515 and is the answer not in the manual?

Buderus Logano G515 Specifications

General IconGeneral
BrandBuderus
ModelLogano G515
CategoryBoiler
LanguageEnglish

Related product manuals