5.9.4 Delay for storing the Min/Max Temperature
A delay time for saving the minimum and maximum temperature can be set to record reliable values when temperatures fluc-
tuate. Here, enter the time span in seconds during which the signal must be continuously present before the temperature is
logged.
Diagnostic
diA
Diagnostics menu
dt.MM
Min/Max Delay
Delay MM
___
0 - 100
Selection menu
Setting range:
0…100 seconds
Use the key to open the list of values.
Set the value with the and keys and use the key to confirm (e.g. 5 (seconds).
The device will return to the submenu.
25Bühler Technologies GmbHBE100022 ◦ 11/2020