EasyManua.ls Logo

Burkert 8700 - Page 24

Burkert 8700
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
Installation and commissioning
Type 8700, 8701, 8703, 8705
7.5.2. Setting the bus address on a device
with rotary switches for setting the
address
(type 8700 / 8701 / 8710 / 8711)
To set an address via the master bus:
Set the switches on an address outside the permitted
range.
Restart the device.
Set the address via the Mass Flow Communicator.
When the device is switched on, the address set with the rotary
switches is accepted as a slave address.
Valid addresses are: • PROFIBUS 0 – 126
• DeviceNet 0 – 63
• CANopen 1 – 127
If the address was set outside the permitted range, the address
setting has the validity as described in chapter 7.5.1
LSB
Unit
position
(x 1)
Unit position Digit times 1
0 – 9
0 – 9
MSB
Decade
position
(x 10)
Decade
position
Digit times
10
0 – 9
0 – 90
A
100
B
110
C
120
D
130
E
140
F
150
The address is composed of LSB + MSB
Example:
Address: MSB setting LSB setting
1 0 1
63 6 3
100 A 0
127 C 7
Fig. 17: Setting the bus address on devices with rotary switch
(types 8700 / 8701 / 8710 / 8711)
English

Related product manuals