55
Periodically inspect all condensate traps in venting
system to ensure they are full of water and in good
condition to maintain a gas-tight seal. Repair, replace
and/or rell traps with water if necessary. Failure to do
so could cause products of combustion and/or carbon
monoxide to enter living space, resulting in severe
personal injury, death or substantial property damage.
Inspecter l’ensemble des collecteur de condensats du
circuit d’évacuation de manière régulière, pour vous
assurer qu’ils soient en bon état et remplis d’eau an
de pouvoir correctement sceller les gaz. Réparer,
remplacer et/ou réalimenter les collecteurs en eau si
nécessaire. Le non-respect des présentes instructions
peut provoquer une fuite de produits combustibles et/
ou de monoxyde de carbone et entraîner des dommages
corporels et matériels sévères, voire la mort.
H. GENERAL MAINTENANCE CONSIDERATIONS
1. Keep radiators and convectors clean.
2. If a hot water radiator is hot at the bottom but not at
the top, it indicates that air has accumulated inside
and should be vented. To vent radiator, hold small
cup under air vent (located near top of radiator),
open vent until water escapes and then close.
3. If much water is added to system, it is advisable to
heat system to a high temperature and vent again.
This will make less venting necessary during the
winter.
4. Where an expansion tank is used, make sure that
neither the tank nor its drain pipe is exposed to
freezing temperatures. Never place valves in piping
leading to or from expansion tank.
5. Boiler and system cleaning will help assure
trouble free operation. See Section IV - Operating
Instructions, Paragraphs F or G for procedure.
I. ATTENTION TO BOILER WHILE NOT IN
OPERATION
If boiler and system is not used during winter time, it
must be fully drained to prevent freeze damage.
Si la chaudière et système n’est pas utilisée pendant
l’hiver, elle doit être entièrement vidangée pour éviter
les dommages causés par le gel.
1. Spray inside surfaces with light lubricating or
crankcase oil using gun with extended stem so as to
reach all corners.
2. Always keep the manual fuel supply valve shut o
when the burner is shut down for an extended period
of time.
3. To recondition the heating system in the fall season
after a prolonged shut down, follow the instructions
outlined in Section IV - Operating Instructions,
Paragraphs B through G.