Pocket RefeRence Guide
— 21
(cont’d)
KEYSTROKE DISPLAY

0.
1. Set to 3-Phase:
(3Ø)
3 PH
2. Set to 60º C:
(60º) 3Ø 60
3 PH
3. Set to Copper (if necessary):
(Cu/Al) 3Ø 60 Cu
3 PH
4. Enter Volts:

VOLT 230.
5. Enter HP:

IND* 10. HP
* Press

until IND is displayed in the
upper left area of the display.
6. Find Full-Load Current:
FLC
28.
A
7. Find 125% Ampacity Wire Size:
(125%)
AWG 8 CU
WIRE SIZE 125%
AMPACITY WIRE SIZING
Wire Sizing is based on Ampacity
requirements used in NEC Tables
310.15(B)(16) and 310.15(B)(17).
Wire Sizing
Wiring is being installed for a 240V,
1Ø system rated at 30 kVA. What is
the 60° C Copper Wire Size?