Installation Manual June 2018 • Rev. 1.6
Key Section & Name
Value
Description
[USBCFG]
[USBCFG]
Key section
DO NOT
change
Password
Cansec
Factory default password. Please
modify to an appropriate password of
your choice other than the default
password.
IP
10.0.0.101
Factory default IP address. Please
Specify the IP address of the host
computer having the
First Access
Express
software installed.
Netmask
255.255.255.0
Factory default subnet mask. Please
specify the subnet mask where the
host computer is connected to.
Gateway
10.0.0.1
Factory default gateway. Please
specify the gateway where the host
computer is connected to.
SrvPort
5000
Factory default server port. You may
change it or leave it as default.
DiagPort
5001
Factory default diagnostic port. You
may change it or leave it as default.
UpdatePort
5002
Factory default update port. You may
change it or leave it as default.
Encryption
0
For future use only.
Authenticate
0
For future use only.
IpSecurity
0
Specify if trusted host is enabled or
disabled. 1=enabled, 0=disabled
ClientIp
0.0.0.0
The IP address of the host computer
having the
First Access Express
software installed. If IpSecurity is
enabled and ClientIp has a valid IP
address specified then the MAP1
controller accepts data connection
(SrvPort 5000) from only this host
computer. Other connections on
DiagPort 5001 and UpdatePort
5002 are not affected by this setting.
Future
blank
For future use only.