Variable Variable name Occup. Description Category
55 Alrm_NetUnit_19.Active 1 Active alarm on unit 19 Alarms
56 Alrm_NetUnit_20.Active 1 Active alarm on unit 20
57 Alrm_WirelessPrb_1_LowBatt.Active 1 Wireless probe 1: Low battery level alarm
58 Alrm_WirelessPrb_2_LowBatt.Active 1 Wireless probe 2: Low battery level alarm
59 Alrm_WirelessPrb_3_LowBatt.Active 1 Wireless probe 3: Low battery level alarm
60 Alrm_WirelessPrb_4_LowBatt.Active 1 Wireless probe 4: Low battery level alarm
61 Alrm_WirelessPrb_Main.Active 1 Wireless probe fault (main group)
62 Alrm_WirelessPrb_Limit.Active 1 Wireless probe fault (limit group)
Tab. 11.g
COIL STATUS
Variable Variable name Occup. Description Category
1 OnBySV 1 Start command from SV (Supervisor) On/Off
7 SchedDayCfg[0].EnTB 1 Scheduler: Enable band 1 Scheduler
8 SchedDayCfg[1].EnTB 1 Scheduler: Enable band 2
9 SchedDayCfg[2].EnTB 1 Scheduler: Enable band 3
10 SchedDayCfg[3].EnTB 1 Scheduler: Enable band 4
11 SchedDayCfg[4].EnTB 1 Scheduler: Enable band 5
12 SchedDayCfg[5].EnTB 1 Scheduler: Enable band 6
Tab. 11.h
11.2.3 Table of BACnet variables
Below are the variables used by the BACnet protocol.
Positive Integer Values
Variable Variable name Access Description Category
0 SV_SWVer R Software version Unit info
1 SV_OSVer R OS version
2 UnitModel R Model version
3 Conductivity R Conductivity Inputs
4 WirelessPrbInfo_1.BattLev R Wireless probe 1: battery level Wireless probes
5 WirelessPrbInfo_1.RadioSignalLev R Wireless probe 1: wireless signal level
6 WirelessPrbInfo_2.BattLev R Wireless probe 2: battery level
7 WirelessPrbInfo_2.RadioSignalLev R Wireless probe 2: wireless signal level
8 WirelessPrbInfo_3.BattLev R Wireless probe 3: battery level
9 WirelessPrbInfo_3.RadioSignalLev R Wireless probe 3: wireless signal level
10 WirelessPrbInfo_4.BattLev R Wireless probe 4: battery level
11 WirelessPrbInfo_4.RadioSignalLev R Wireless probe 4: wireless signal level
12 UnitStatus R Unit status Unit status
13 WorkHr R Unit operating hours
14 CylWorkHr R Cylinder operating hours
15 ManMode RW Manual mode (1=outputs, 2=request) Manual
16 ManSSR_OpT RW SSR opening time (manual mode)
17 ManSSR_ClT RW SSR closing time (manual mode)
18 RegulationCfg.RegTyp RW Control type Reg cfg
19 ThrshAlrmDT RW High humidity/temperature alarm delay Alrm thr.
20 MainPrbCfg.Typ RW Main probe type IO cfg
21 LimitPrbCfg.Typ RW Limit probe type
22 WHardnessMan RW Manual water hardness value (if WHardnessTyp is TRUE) Unit cfg
23 EvapCycleNoThrshsh RW Number of evaporation cycles (0=auto)
24 FillTScale RW Variation in fi ll time
25 DilDrainTScale RW Variation in drain time
26 Scheduler.SchedDayToSet RW When >0, day of the week to be confi gured (1=Monday, 7=Sunday) Scheduler
27 SchedDayCfg[0].StartHr RW Band 1 start hours
28 SchedDayCfg[0].StartMin RW Band 1 start minutes
29 SchedDayCfg[0].WorkMode RW Band 1 operating mode
30 SchedDayCfg[1].StartHr RW Band 2 start hours
31 SchedDayCfg[1].StartMin RW Band 2 start minutes
32 SchedDayCfg[1].WorkMode RW Band 2 operating mode
33 SchedDayCfg[2].StartHr RW Band 3 start hours
34 SchedDayCfg[2].StartMin RW Band 3 start minutes
35 SchedDayCfg[2].WorkMode RW Band 3 operating mode
36 SchedDayCfg[3].StartHr RW Band 4 start hours
37 SchedDayCfg[3].StartMin RW Band 4 start minutes
38 SchedDayCfg[3].WorkMode RW Band 4 operating mode
39 SchedDayCfg[4].StartHr RW Band 5 start hours
40 SchedDayCfg[4].StartMin RW Band 5 start minutes
41 SchedDayCfg[4].WorkMode RW Band 5 operating mode
42 SchedDayCfg[5].StartHr RW Band 6 start hours
43 SchedDayCfg[5].StartMin RW Band 6 start minutes
44 SchedDayCfg[5].WorkMode RW Band 6 operating mode
45 UoM RW Unit of measure UoM
46 Year RW Year Clock
47 Month RW Month
48 Day RW Day
49 Hour RW Hour
50 Minute RW Minutes
51 SetTimezone RW Time zone