EasyManua.ls Logo

Carel heaterSteam - Page 54

Carel heaterSteam
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
54
ENG
“heaterSteam +0300080EN - rel. 1.0 - 27.04.2016
Binary Values
Variable Variable name Access Description Category
0 RemOn R Remote on/off I/O
1 ThermPtcDin R Thermal DIN status
2 LevSenStatus.Low R Level sensor: low level
3 LevSenStatus.Hi R Level sensor: high level
4 LevSenStatus.Foam R High level sensor: foam
5 OnOff Status R Unit status On or OFF On/O
6 OnBySV RW Start command from SV (Supervisor)
12 PreMainWarn R Maintenance pre-alert (not an alarm) Alarms
13 CurrBlkAlrm.IsBlocker R Shutdown alarm
14 CurrBlkAlrm.IsPresent R Resettable alarm
15 CurrBlkAlrm.Warning R Warning
16 Alrm_Autotest.Active R Autotest alarm
17 Alrm_HighConductAl.Active R High conductivity alarm
18 Alrm_LevSen.Active R Level sensor broken alarm
19 Alrm_ThermPtc.Active R Thermal overload alarm
20 Alrm_Wmiss.Active R No water alarm
21 Alrm_LowProd.Active R Low production alarm
22 Alrm_MainPrb.Active R Main probe fault alarm
23 Alrm_LimPrb.Active R Limit probe fault alarm
24 Alrm_PreHPrb.Active R NTC preheating probe fault alarm
25 Alrm_HiHum.Active R High humidity alarm
26 Alrm_LoHum.Active R Low humidity alarm
27 Alrm_HiHumLim.Active R High humidity limit alarm
28 Alrm_Foam.Active R Foam alarm
29 Alrm_PeriodicMaint.Active R Periodical maintenance request
30 Alrm_CylFull.Active R Cylinder full alarm
31 Alrm_ConductPrb.Active R Conductivity probe fault alarm
32 Alrm_HighConductWr.Active R High conductivity warning
33 Alrm_RetMem.Active R Retain memory damaged warning
34 Warn_Autotest.Active R Autotest warning
35 Warn_LevSen.Active R Level sensor warning
36 Warn_LowProd.Active R Low production warning
37 Alrm_WirelessPrb_1_Offl ine.Active R Wireless probe 1 offl ine
38 Alrm_WirelessPrb_2_Offl ine.Active R Wireless probe 2 offl ine
39 Alrm_WirelessPrb_3_Offl ine.Active R Wireless probe 3 offl ine Alarms
40 Alrm_WirelessPrb_4_Offl ine.Active R Wireless probe 4 offl ine
41 Alrm_MissingModel.Active R Model not confi gured
42 Alrm_NetUnit_1.Active R Active alarm on unit 1
43 Alrm_NetUnit_2.Active R Active alarm on unit 2
44 Alrm_NetUnit_3.Active R Active alarm on unit 3
45 Alrm_NetUnit_4.Active R Active alarm on unit 4
46 Alrm_NetUnit_5.Active R Active alarm on unit 5
47 Alrm_NetUnit_6.Active R Active alarm on unit 6
48 Alrm_NetUnit_7.Active R Active alarm on unit 7
49 Alrm_NetUnit_8.Active R Active alarm on unit 8
50 Alrm_NetUnit_9.Active R Active alarm on unit 9
51 Alrm_NetUnit_10.Active R Active alarm on unit 10
52 Alrm_NetUnit_11.Active R Active alarm on unit 11
53 Alrm_NetUnit_12.Active R Active alarm on unit 12
54 Alrm_NetUnit_13.Active R Active alarm on unit 13
55 Alrm_NetUnit_14.Active R Active alarm on unit 14
56 Alrm_NetUnit_15.Active R Active alarm on unit 15
57 Alrm_NetUnit_16.Active R Active alarm on unit 16
58 Alrm_NetUnit_17.Active R Active alarm on unit 17
59 Alrm_NetUnit_18.Active R Active alarm on unit 18
60 Alrm_NetUnit_19.Active R Active alarm on unit 19
61 Alrm_NetUnit_20.Active R Active alarm on unit 20
62 Alrm_WirelessPrb_1_LowBatt.Active R Wireless probe 1: Low battery level alarm
63 Alrm_WirelessPrb_2_LowBatt.Active R Wireless probe 2: Low battery level alarm
64 Alrm_WirelessPrb_3_LowBatt.Active R Wireless probe 3: Low battery level alarm
65 Alrm_WirelessPrb_4_LowBatt.Active R Wireless probe 4: Low battery level alarm
66 Alrm_WirelessPrb_Main.Active R Wireless probe fault (main group)
67 Alrm_WirelessPrb_Limit.Active R Wireless probe fault (limit group)
68 SchedDayCfg[0].EnTB RW Scheduler: Enable band 1 Scheduler
69 SchedDayCfg[1].EnTB RW Scheduler: Enable band 2
70 SchedDayCfg[2].EnTB RW Scheduler: Enable band 3
71 SchedDayCfg[3].EnTB RW Scheduler: Enable band 4
72 SchedDayCfg[4].EnTB RW Scheduler: Enable band 5
73 SchedDayCfg[5].EnTB RW Scheduler: Enable band 6
Tab. 11.j

Table of Contents

Related product manuals