54
ENG
“heaterSteam” +0300080EN - rel. 1.0 - 27.04.2016
Binary Values
Variable Variable name Access Description Category
0 RemOn R Remote on/off I/O
1 ThermPtcDin R Thermal DIN status
2 LevSenStatus.Low R Level sensor: low level
3 LevSenStatus.Hi R Level sensor: high level
4 LevSenStatus.Foam R High level sensor: foam
5 OnOff Status R Unit status On or OFF On/Off
6 OnBySV RW Start command from SV (Supervisor)
12 PreMainWarn R Maintenance pre-alert (not an alarm) Alarms
13 CurrBlkAlrm.IsBlocker R Shutdown alarm
14 CurrBlkAlrm.IsPresent R Resettable alarm
15 CurrBlkAlrm.Warning R Warning
16 Alrm_Autotest.Active R Autotest alarm
17 Alrm_HighConductAl.Active R High conductivity alarm
18 Alrm_LevSen.Active R Level sensor broken alarm
19 Alrm_ThermPtc.Active R Thermal overload alarm
20 Alrm_Wmiss.Active R No water alarm
21 Alrm_LowProd.Active R Low production alarm
22 Alrm_MainPrb.Active R Main probe fault alarm
23 Alrm_LimPrb.Active R Limit probe fault alarm
24 Alrm_PreHPrb.Active R NTC preheating probe fault alarm
25 Alrm_HiHum.Active R High humidity alarm
26 Alrm_LoHum.Active R Low humidity alarm
27 Alrm_HiHumLim.Active R High humidity limit alarm
28 Alrm_Foam.Active R Foam alarm
29 Alrm_PeriodicMaint.Active R Periodical maintenance request
30 Alrm_CylFull.Active R Cylinder full alarm
31 Alrm_ConductPrb.Active R Conductivity probe fault alarm
32 Alrm_HighConductWr.Active R High conductivity warning
33 Alrm_RetMem.Active R Retain memory damaged warning
34 Warn_Autotest.Active R Autotest warning
35 Warn_LevSen.Active R Level sensor warning
36 Warn_LowProd.Active R Low production warning
37 Alrm_WirelessPrb_1_Offl ine.Active R Wireless probe 1 offl ine
38 Alrm_WirelessPrb_2_Offl ine.Active R Wireless probe 2 offl ine
39 Alrm_WirelessPrb_3_Offl ine.Active R Wireless probe 3 offl ine Alarms
40 Alrm_WirelessPrb_4_Offl ine.Active R Wireless probe 4 offl ine
41 Alrm_MissingModel.Active R Model not confi gured
42 Alrm_NetUnit_1.Active R Active alarm on unit 1
43 Alrm_NetUnit_2.Active R Active alarm on unit 2
44 Alrm_NetUnit_3.Active R Active alarm on unit 3
45 Alrm_NetUnit_4.Active R Active alarm on unit 4
46 Alrm_NetUnit_5.Active R Active alarm on unit 5
47 Alrm_NetUnit_6.Active R Active alarm on unit 6
48 Alrm_NetUnit_7.Active R Active alarm on unit 7
49 Alrm_NetUnit_8.Active R Active alarm on unit 8
50 Alrm_NetUnit_9.Active R Active alarm on unit 9
51 Alrm_NetUnit_10.Active R Active alarm on unit 10
52 Alrm_NetUnit_11.Active R Active alarm on unit 11
53 Alrm_NetUnit_12.Active R Active alarm on unit 12
54 Alrm_NetUnit_13.Active R Active alarm on unit 13
55 Alrm_NetUnit_14.Active R Active alarm on unit 14
56 Alrm_NetUnit_15.Active R Active alarm on unit 15
57 Alrm_NetUnit_16.Active R Active alarm on unit 16
58 Alrm_NetUnit_17.Active R Active alarm on unit 17
59 Alrm_NetUnit_18.Active R Active alarm on unit 18
60 Alrm_NetUnit_19.Active R Active alarm on unit 19
61 Alrm_NetUnit_20.Active R Active alarm on unit 20
62 Alrm_WirelessPrb_1_LowBatt.Active R Wireless probe 1: Low battery level alarm
63 Alrm_WirelessPrb_2_LowBatt.Active R Wireless probe 2: Low battery level alarm
64 Alrm_WirelessPrb_3_LowBatt.Active R Wireless probe 3: Low battery level alarm
65 Alrm_WirelessPrb_4_LowBatt.Active R Wireless probe 4: Low battery level alarm
66 Alrm_WirelessPrb_Main.Active R Wireless probe fault (main group)
67 Alrm_WirelessPrb_Limit.Active R Wireless probe fault (limit group)
68 SchedDayCfg[0].EnTB RW Scheduler: Enable band 1 Scheduler
69 SchedDayCfg[1].EnTB RW Scheduler: Enable band 2
70 SchedDayCfg[2].EnTB RW Scheduler: Enable band 3
71 SchedDayCfg[3].EnTB RW Scheduler: Enable band 4
72 SchedDayCfg[4].EnTB RW Scheduler: Enable band 5
73 SchedDayCfg[5].EnTB RW Scheduler: Enable band 6
Tab. 11.j