EasyManuals Logo

Carel IR Series User Manual

Carel IR Series
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
Le modifiche da apportare sono:
Modo di partenza: C0=2
ingresso digitale 1: gestione allarme con blocco uscite e
attivazione uscita di allarme.
C29=2 allarme immediato con Reset manuale;
C31=0 in caso di allarme da ingresso digitale tutte le uscite ven-
gono spente.
OUT1:
uscita ON/OFF per comando del primo bruciatore:
INSERZIONE=C36=-33 DIFFERENZIALE/LOGICA=C37=33
(DIPENDENZA e TIPO DI USCITA invariati)
OUT2:
uscita ON/OFF per comando del secondo bruciatore:
INSERZIONE=C40=-66 DIFFERENZIALE/LOGICA=C41=33
(DIPENDENZA e TIPO DI USCITA invariati)
OUT3:
uscita ON/OFF per comando del terzo bruciatore:
INSERZIONE=C44=-100 DIFFERENZIALE/LOGICA=C45=34
(DIPENDENZA e TIPO DI USCITA invariati)
OUT4:
uscita ON/OFF d’allarme di “Alta” e da blocco esterno.
DIPENDENZA C46=5 (o 6 se si preferisce il relè normalmente eccitato)
P26 = livello di “Alta” temperatura richiesto (Es. 90°C)
P27 = differenziale allarme (visto che l’allarme deve essere
assoluto, P27 deve essere positivo)
P28 = eventuale ritardo allarme temperatura e blocco
Il grafico raffigura la logica di funzionamento selezionata.
Esempio 14
In un impianto di stagionatura si controlli la temperatura tramite
un compressore (generatore di freddo) ed una resistenza elet-
trica (generatore di calore). Il controllo deve agire con una zona
neutra di 3 °C attorno ad un set di 5 °C.
Il comando della resistenza dovrà essere di tipo PWM per un
inserimento proporzionale della potenza.
Soluzione: Modo di partenza: C0=3 salvare la modifica uscendo
dalla programmazione con PRG, rientrare in programmazione,
P.W.77, ponendo C33=1;
St1=5°C – P3=1,5°C P1 e P2 stabiliranno il differenziale di lavoro
rispettivamente della resistenza e del compressore.
OUT1: comando della resistenza con funzionamento PWM;
TIPO DI USCITA=C35=1, per funzionamento PWM (DIPENDENZA,
INSERZIONE e DIFFERENZIALE/LOGICA invariati).
OUT2: uscita ON/OFF per comando del compressore: resta
invariata.
In short:
Starting Mode: C0=2;
Digital input no.1: alarm management with output disenergiza-
tion and energization of the alarm output;
C29=2: immediate alarm, manual reset;
C31=0: in the event of off-normal condition, all outputs will
disenergise;
OUT1:
ON/OFF output to control the first burner unit
ENERGIZATION=C36=-33 DIFFERENTIAL/LOGIC=C37= 33
(Dependence and Type of Output remain unchanged).
OUT2:
ON/OFF output to control the second burner unit
ENERGIZATION=C40=-66 DIFFERENTIAL/LOGIC=C41= 33
(Dependence and Type of Output remain unchanged).
OUT3:
ON/OFF output to control the third burner unit
ENERGIZATION=C44=-100 DIFFERENTIAL/LOGIC=C45=
34(Dependence and Type of Output remain unchanged).
OUT4:
ON/OFF output for high temperature alarm and external system lock.
DEPENDENCE C46=5 (or 6 if you prefer a normally energized relay);
P26=sets the required high temperature level (e.g. 90°C);
P27=alarm differential (P27 must be a positive value);
P28=time-delay (if any) before the activation of the temperature/
system lock alarm.
The graph below illustrates the new control logic:
Example no. 14
Control and regulation of the temperature of a cold storage
room by means of a compressor (cooling function) and an elec-
tric heater (heating function). The controller will develop correc-
tive action in response to deviation from the desired conditions,
according to the set values, that is neutral zone=3°C and set-
point=5°C. The heater operates in the PWM logic so as to obtain a
proportional operating logic.
Solution: Starting Mode: C0=3: Confirm the modification by
exiting the programming field through PRG, then enter again
(password 77) and set C33=1; St1=5°C – P3=1.5°C
P1 and P2 represent the operating differential of heater and
compressor respectively.
OUT1: Control of the heater, PWM logic; TYPE OF
OUTPUT=C35=1, PWM function (DEPENDENCE, ENERGIZATION
and DIFFERENTIAL/LOGIC remain unchanged).
OUT2: ON/OFF output for the control of the compressor
(unchanged)
54
Fig.41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel IR Series and is the answer not in the manual?

Carel IR Series Specifications

General IconGeneral
DisplayLCD
TypeController
CommunicationModbus
SeriesIR Series
CategoryController

Related product manuals