11ir33 platform “connections” +030220445 - rel. 2.3 - 27.04.2011
Tab. 2.a
ENGLISH
Case plastic: dimensions 36x167x51 mm; mounting depth 40 mm
Assembly smooth, hard and indeformable panel: using screws from the front
drilling template: dimensions 29x138.5 mm; distance between fastening screws 153.5 mm
fastening screws: countersunk head with maximum thread diameter 3.9 mm
Wide vers. case
(power supply S)
plastic dimensions: 39.4x183x45
mounting depth 40 mm
Assembly smooth, hard and indeformable panel using screws from the front or brackets
(power supply S)
Wide versions
drilling template dimensions: from 138.5x29 to150x31
distance between fastening screws: 165 mm or 153.5
fastening screws countersunk head with maximum thread diameter 3.9 mm for 165 mm spacing
fl at head for 153 mm spacing, maximum thread diameter 3 mm
Display digits: 3 digit LED
display: from -99 to 999
operating status: indicated with graphic icons on the display
Keypad 8 silicone rubber buttons
Infrared receiver available depending on the model
Clock with backup battery available depending on the model
Buzzer available in all models
Clock Error at 25 °C: ± 10 ppm (±5.3 min/year)
Error in the temperature range –10T60 °C: - 50ppm (-27min/year)
Ageing: < ±5p pm (±2.7 min/year)
Discharge time: typically 6 months (8 months maximum)
Recharge time: typically 5 hours (< 8 hours maximum)
Operating conditions -10T65 °C; <90% relative umidity non-condensing
Storage conditions -20T70 °C; <90% relative umidity non-condensing
Front panel index of protection assembly on smooth and indeformable panel with IP65 gasket
Environmental pollution 2, normal situation
PTI of insulating materials printed circuits 250, plastic and insulating materials 175
Period of stress across the insulating parts long
Category of resistance to fi re category D and category B (UL 94-V0)
Class of protection against voltage surges category II
Type of action and disconnection 1B relay contacts (micro-disconnection)
Construction of the control device electronic control device incorporated
Classifi cation according to protection
against electric shock
to be integrated into class I appliances
Device designed to he hand-held or
integrated into equipment designed to
be hand-held
no
Software class and structure class A
Cleaning the front panel of the
instrument
only use neutral detergents and water
Serial interface for CAREL network External, available in all models
Interface for repeater display External, available in all models
Maximum distance between interface
and display
10 m
Programming key Available in all models
Table 2.a