Parameter categories visible on the user terminal
VIS
(Display)
CtL
(Control)
DEF
(Defrost)
ALM
(Alarms)
FAN
(Fans)
EVD (Electronic exp.
valve)
CnF
(Configuration)
Sm PPU On d0 AA F0 P1 H0
Sd tGS St dI A0 F1 P3 H2
Sr tEu rd dt1 AL Frd P7 H1
Sa PEu ESC dP1 AH ESC ESC ESC
Sv ESC ESC Ad
Svt ESC
Procedure
To navigate the menu tree, use the following buttons:
l UP and DOWN to navigate the menu and set the values;
l PRG to enter the menu items and save the changes made;
l PRG (3s) to select the menu item or ESC to return to the previous branch.
Example of how to set parameter St (set point):
1. Wait for the standard display to be
shown;
2. Press PRG for 3 s: the password
prompt is displayed (PSd)
3. Press PRG: UP and DOWN flash
4. Press UP and enter the password:
33
5. Press PRG: the first category of
parameters is displayed: VIS
(=Display)
6. Press DOWN: the second
category of parameters is
displayed: Ctl (=Control)
7. Press DOWN until reaching
parameter St (=set point) and PRG to
display the value
8. Press UP/DOWN to modify the
value
9. Press PRG to save the setting
and return to the parameter code
10. Press PRG for 3 s or alternatively, in
the parameter level select ESC and
press PRG to return to the parameter
categories
11. Press DOWN to move to the
next category dEF (=Defrost)
and follow steps 5 to 9 to set the
other parameters
12. After having completed the
settings, to exit either: a) from the
categories press ESC and then
PRG; or b) press PRG for 3 s
Note: if no button is pressed, after around 1 minute the terminal will automatically return to the
standard display.
Mobile device and PC
The Applica app and SPARK software can be used to configure the controller from a mobile device
(smartphone, tablet), via NFC (Near Field Communication) or Bluetooth (in this case also by laptop). The
controller can be programmed according to the profile used for access to APPLICA or SPARK, with