Code Description Def Min Max UOM User
User
terminal
0 = function disabled
rHt
Manual anti-sweat heater activation period
0 = function disabled
5 0 180 min S NO
CLt Max time for Clean status 0 0 999 min U NO
Stt Maximum time for Standby status 0 0 240 min S NO
H14 Time light stays on after closing the door 0 0 240 min U NO
dbS Safety timeout for double thermostat function 0 0 240 min M NO
db1
Double thermostat function logic
0/1: AND logic/OR logic
0 0 1 - M NO
rSu Suction valve closing delay in normal control mode 0 0 999 s S NO
Defrost
d0
Type of defrost
0 = heater by temperature
1 = reserved
2 = heater by time
3 = reserved
4 = heater by time with temperature control
0 0 4 - S YES
d2
End defrost synchronised by Master
0/1 = not synchronised/synchronised
1 0 1 - S NO
d3
Send network start defrost command (for Master)
0/1: yes/no
Ignore network start defrost command (for Slave)
0/1: no/yes
0 0 1 - S NO
dI Maximum interval between consecutive defrosts 8 0 240 hours S YES
dt1 End defrost temperature (read by Sd) 8 -50 50 °C/°F S YES
dt2 End defrost temperature (read by Sd2) 8 -50 50 °C/°F S NO
dP1 Maximum defrost duration 45 1 240 min S YES
dP2 Max secondary evap. defrost duration 45 1 240 min S NO
d4
Defrost on power-up (Master = network defrost; Slave = local defrost)
0/1 = No/Yes
0 0 1 - S NO
d5
Defrost delay on power-up or (for Slave) after control from Master
0 = delay disabled
0 0 240 min S NO
d6
Display on terminals during defrost
0 = temperature alternating with ‘dEF
1 = freeze display
2 = ‘dEF
1 0 2 - U NO
dd
Dripping time after defrost (fans off)
0 = no dripping
2 0 15 min S NO
d7
Skip defrost
0/1 = disabled/enabled
0 0 1 - S NO
d8 Bypass high temperature alarm time after defrost 30 1 240 min S NO
d9
Defrost priority over compressor protection times
0/1 = protection times observed/protection times not observed
1 0 1 - M NO
d10
Defrost time in Running time mode
0 = function disabled
0 0 240 min S NO
d11 Defrost temperature threshold in Running time mode -30 -50 50 °C/°F S NO
d12
Pressure probe alarm management during defrost
probe error supervisor update
0 disabled enabled
1 enabled enabled
2 disabled disabled
3 enabled disabled
0 0 3 - M NO
dH1
Pump down phase duration
0 = pump down disabled
0 0 999 s M NO
dS1
Compressor off time in sequential stop defrost mode
0 = function disabled
0 0 45 min M NO
88|6. Parameter table
MPXone +0300086EN rel. 1.0 04.09.2018