Mask index Display Description Description Default UOM Values
Dbd01
Enable condensing
setpoint compensation
Enable setpoint compensation (condenser line 2)
NO --- NO / YES
……
Dbe01
Cond.temperature/pres-
sure high alarm
Type of high condensing pressure/temperature alarm threshold
(line 2)
ABSOLUTE --- ABSOLUTE / RELATIVE
Threshold High condensing pressure/temperature alarm threshold (line 2) 24.0 barg …(**)
……
Dbf01 Number of present fans Number of fans (line 2) 3 --- 0…16
……
Dbg01
Modulate speed device Fan driver type (line 2)
NONE ---
NONE
INVETER
PHASE CONTROL
……
Mask index
Display description Description
Default UOM Values
E.Other funct. (The I/Os available depend on the selected confi guration, the following are just some examples. For the complete list of I/O positions available see Appendix
A.5)
Eaaa04
--- Oil temperature probe position (line1)
B1 ---
---, B1…B10 (****)
--- Oil temperature probe type (line 1)
4...20mA ---
---
NTC - PT1000 - 0-1V - 0-10V -
4...20mA - 0-5V - HTNTC
--- (display only) Oil temperature probe value (line 1)
---
… (**)
Upper value Oil temperature probe max. limit (line 1) 30.0 barg … (**)
Lower value Oil temperature probe min. limit (line 1) 0.0 barg … (**)
Calibration Oil temperature probe adjustment (line 1) 0.0 barg … (**)
……
Eaaa45
DO Oil level valve DO position, compressor 6 (line 1) 03 --- ---, 01…29 (****)
Status (display only) Oil level valve DO status, compressor 6 (line 1) --- --- Closed / Open
Logic Oil level valve DO logic, compressor 6 (line 1) NC --- NC / NO
Function (display only) Oil level function status, compressor 6 (line 1) --- --- Not active / Active
Eaab04
Common oil cooler Enable common oil cooling (line 1) SI --- NO / YES
Oil pumps number Number of oil pumps for common oil cooler (line 1)
0 ---
0 to 1 (Analog output)
0 to 2 (Digital outputs)
Enable Aout pump Enable AO of common oil cooler pump (line 1)
SI ---
NO (Digital outputs)
YES (Analog output)
Eaab05
Setpoint Common oil cooler setpoint (line 1) 0.0 °C … (**)
Diff erential Common oil cooler diff erential (line 1) 0.0 °C -9.9…9.9
Eaab06
Pump start delay Time delay before the start-up of pump 2 after pump1 turns on
(line 1)
0 s
0…999
Eaab07
Oil pumps number Screw compressors: number of oil cooler pumps enabled (line1)
0 ---
0 to 1 (Analog output)
0 to 2 (Digital outputs)
Enable Aout pump Screw compressors: enable AO for oil cooler pump (line 1)
SI ---
NO (Digital outputs)
YES (Analog output)