13
ENG
“UEX-PLUS” +0300040EN - rel. 1.4 - 25.09.2015
installeruserservice
3. STEAM DISTRIBUTION
3.1 CAREL jet distributors (SDPOEM00**)
These can be fi tted horizontally or vertically (hole facing upwards).
See page 42 for the models of distributors.
Assembly instructions (see Fig.3.a):
• make a series of holes on the wall according to the distributor drilling
template;
• insert the distributor;
• fasten the fl ange using 4 screws.
31,5
50 50
31,5
50
31,531,5
57,5
100
C
D
C
A
A
B
B
Fig. 3.a
Key:
A. steam inlet
B. condensate drain
C. steam outlet.
the dimensions of the hole vary depending on the models of
distributor:
model SDPOEM0000: hole made manually, up to 30 mm (1.2”) in
diameter);
model SDPOEM0012: diameter of the hole 12 mm (0.5”);
model SDPOEM0022: diameter of the hole 22 mm (0.9”).
D drilling template
Note: if steam hoses with an inside diameter of 30 mm (1.2”) are
used, remove the 22 mm (0.9”) steam inlet section.
3.2 CAREL linear distributors for air ducts
(DP***DR0)
Install away from obstacles (curves, branches, changes in cross-section,
grills, fi lters, fans).
Minimum distance between the distributor and the obstacle: 1/1.5 m
(3.3/4.9 ft). Increase the distance if:
• the air speed increases in the duct,
• the relative humidity of the air increases before and after humidifi cation,
• the turbulence decreases.
See page 42 for installation examples.
Assembly instructions (see Fig.3.b):
• make a series of holes on the wall according to the distributor drilling
template (included in the packaging with the distributor);
• fasten the fl ange using 4 screws.
A 22
B 10
Y 58
35
X 68
dimensio
B
Y
X
A
X
°2
1
2
3
4
5
6
8
7
Fig. 3.b
Key:
1 “L”-shaped mounting support (where featured)
2 fl ange gasket
3 steam inlet (ØA)
4 condensate drain (ØB)
5 screw diameter (see the instruction sheet supplied with the distributor)
6 length (depending on the model of distributor, see par. “10.5” page 42)
7 angle (around 2°) for draining the condensate.
8 diameter of the hole on the wall (ØY)
Dimensions in mm (in)
CAREL linear distributors
DP***D22R0 DP***D30R0 DP***D40R0
ØA 22 (0.9”) 30 (1.18”) 40 (1.57”)
ØB 10 (0.4”) 10 (0.4”) 10 (0.4”)
ØY 58 (2.3”) 68 (2.7”) 89 (3.5”)
Ø 35 (1.4”) 45 (1.8”) 60 (2.4”)
X 68 (2.7”) 77 (3.0”) 99 (3.9”)
Tab. 3.a
Important:
1. fi t the distributor at a slight incline (at least 2°, to prevent the return of
condensate);
2. the “L”-shaped mounting support (see part 1 Fig. 3.c) is supplied with
steam distributor models from DP085* to DP025*. For shorter lengths,
the support can be supplied as an option (code 18C478A088).
3.3 CAREL steam blowers (VSDU0A*, models
UE001 to UE018 only)
Steam distributors for humidifi ers with fl ow rates up to 18 kg/h (39.7
lb/h). Can be connected on top of the humidifi er, or separately in another
location (see the fi gure below).
A
B
C
D
E
F
G
DIMENSIONI (m) A B C D
>0,5 >5 ≥2,1 >1
DIMENSIONI (m) E F G
>0,5 >5 >1
Fig. 3.c