EasyManua.ls Logo

Carel UE001 - 3. STEAM DISTRIBUTION

Carel UE001
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
ENG
“UEX-PLUS” +0300040EN - rel. 1.4 - 25.09.2015
installeruserservice
3. STEAM DISTRIBUTION
3.1 CAREL jet distributors (SDPOEM00**)
These can be fi tted horizontally or vertically (hole facing upwards).
See page 42 for the models of distributors.
Assembly instructions (see Fig.3.a):
make a series of holes on the wall according to the distributor drilling
template;
insert the distributor;
fasten the fl ange using 4 screws.
31,5
50 50
31,5
50
31,531,5
57,5
100
C
D
C
A
A
B
B
Fig. 3.a
Key:
A. steam inlet
B. condensate drain
C. steam outlet.
the dimensions of the hole vary depending on the models of
distributor:
model SDPOEM0000: hole made manually, up to 30 mm (1.2”) in
diameter);
model SDPOEM0012: diameter of the hole 12 mm (0.5”);
model SDPOEM0022: diameter of the hole 22 mm (0.9”).
D drilling template
Note: if steam hoses with an inside diameter of 30 mm (1.2”) are
used, remove the 22 mm (0.9”) steam inlet section.
3.2 CAREL linear distributors for air ducts
(DP***DR0)
Install away from obstacles (curves, branches, changes in cross-section,
grills, fi lters, fans).
Minimum distance between the distributor and the obstacle: 1/1.5 m
(3.3/4.9 ft). Increase the distance if:
the air speed increases in the duct,
the relative humidity of the air increases before and after humidifi cation,
the turbulence decreases.
See page 42 for installation examples.
Assembly instructions (see Fig.3.b):
make a series of holes on the wall according to the distributor drilling
template (included in the packaging with the distributor);
fasten the fl ange using 4 screws.
A 22
B 10
Y 58
35
X 68
dimensio
n
B
Y
X
A
X
°2
1
2
3
4
5
6
8
7
Fig. 3.b
Key:
1 “L”-shaped mounting support (where featured)
2 ange gasket
3 steam inlet (ØA)
4 condensate drain (ØB)
5 screw diameter (see the instruction sheet supplied with the distributor)
6 length (depending on the model of distributor, see par. “10.5” page 42)
7 angle (around 2°) for draining the condensate.
8 diameter of the hole on the wall (ØY)
Dimensions in mm (in)
CAREL linear distributors
DP***D22R0 DP***D30R0 DP***D40R0
ØA 22 (0.9”) 30 (1.18”) 40 (1.57”)
ØB 10 (0.4”) 10 (0.4”) 10 (0.4”)
ØY 58 (2.3”) 68 (2.7”) 89 (3.5”)
Ø 35 (1.4”) 45 (1.8”) 60 (2.4”)
X 68 (2.7”) 77 (3.0”) 99 (3.9”)
Tab. 3.a
Important:
Important:
1. t the distributor at a slight incline (at least 2°, to prevent the return of
condensate);
2. the “L”-shaped mounting support (see part 1 Fig. 3.c) is supplied with
steam distributor models from DP085* to DP025*. For shorter lengths,
the support can be supplied as an option (code 18C478A088).
3.3 CAREL steam blowers (VSDU0A*, models
UE001 to UE018 only)
Steam distributors for humidifi ers with fl ow rates up to 18 kg/h (39.7
lb/h). Can be connected on top of the humidifi er, or separately in another
location (see the fi gure below).
A
B
C
D
E
F
G
DIMENSIONI (m) A B C D
>0,5 >5 ≥2,1 >1
DIMENSIONI (m) E F G
>0,5 >5 >1
Fig. 3.c
Important:
Important:
For correct distribution of the steam, observe
For correct distribution of the steam, observe
the distance shown in the fi gure above.

Table of Contents