26
ENG
“UEX-PLUS” +0300040EN - rel. 1.4 - 25.09.2015
installeruserservice
8.6 Supervisor
parameter range def. UOM
identifi cation
number for BMS
network
0 to 200 1
Com. speed
1200, 2400, 4800, 9600,
19200
19200 Bps
Protocol
CAREL, MODBUS,
LON, RS232, GSM(*),
WINLOAD
CAREL
Enable On/OFF from
supervisor
SI/NO NO
(*)
By setting the GSM protocol, when alarms are activated the humidifi er
sends an SMS (short message service) to the mobile telephone number
set.
1. Important: to send an SMS, the humidifi er must be fi tted with
the electronic board code PCO100MDM0, the GSM modem
kit code PLW0PGSM00, and a SIM card in the modem (see par. “GSM
network connection” page 17).
“SMS” con guration procedure
• set the GSM protocol from the “Supervisor” screen (see “Supervisor”
screen > “Protocol”);
• press ENTER until the cursor is at the start of the screen;
• press the DOWN button and access the “SMS” screen;
• confi gure the “SMS” screen:
SMS
parameter range default
text on mask send SMS
enter text(*) CAREL HUMISTEAM
mobile number
enter mobile phone
number (*)
-
modem status (display only)
parameter display default
fi eld
percentage of signal -
alarm modem
NO/YES -
(*) Text characters:
ABCDEF GHI J KL
MNOP QR S T UV WX
YZ0123456789
+-*:;,()/#%
Function buttons:
• UP or DOWN to select the characters;
• ENTER to save and move the cursor to the next character.
Important: the humidifi er only has one communication line
(baud rate and protocol). When enabling SMS messages, a
supervisory network can not be created (and vice-versa).
Important:
• only use numeric characters;
• disable the PIN code on the SIM card;
• messages can only be sent in SMS format;
• the SMS messages are subject to the charges and conditions of the SIM
card network operator.
CAREL declines all liability for the failure to send or receive SMS.