35
ENG
“UEX-PLUS” +0300040EN - rel. 1.4 - 25.09.2015
Table of water circuit, electrical and electronic spare parts, UE090 to
UE130
description spare part code position g.
UE090 UE130
Water circuit
Drain pump hose UEKDH00000 7 11.e
Manifold UEKCOLL000 6 11.e
Drain pump kit KITPSE0000 5 11.e
Internal tubing kit UEKT100XXL 3 11.e
Double check valve kit FWHDCV0000 -
Conductivity meter kit KITCN00000 4 11.e
Fill solenoid valve kit KITVC10140 2 11.e
Drain circuit UEKDC20000 1 11.e
Electrical and electronics
Display terminal HCT1EXW000 18 11.f
TAM (current transformer) UEKTAM0000 11 11.f
Contactor URKCONT300 11.f
Power transformer UEKTR20000 11 11.f
Electronic controller
(1)
UEXzzv001i
(2)
14 11.f
Fuse carrier URKFH20000 13 11.f
Pump control relay UEKRD00000 12 11.f
F1 - F2 power fuses UEKFUSE300 - see electrical diagram
F3 Pump fuse URKFUSE300 - see electrical diagram
F4 Transformer secondary fuse UEKFUSE400 - see electrical diagram
Connection cable between terminal and electronic controller S90CONN002 -
Tab. 11.f
(1)
To make an order specify the complete product code and the serial number of your
humidifer.
(2)
zz: board version
0A: basic version not confi gured up to UE65 model
0B: with expantion board not confi gured for UE90-130 models
01,.....,90 kg/h
A3= 130 Kg/h
v: voltage
i: 0 single packing; 1: multiple packing
Table of spare parts for standard and special cylinders UE090 to UE130
Description UE090 UE130
STANDARD disposable cylinders 400 V 3ph cylinder, conductivity 350 to 1250 μS/cm BL0T4C00H2 BL0T5C00H0
SPECIAL disposable cylinders 400 V 3ph cylinder, conductivity 75 to 350 μS/cm BL0T4B00H2 BL0T5B00H0
SPECIAL openable cylinder 400 V 3ph cylinder, conductivity 75 to 350 μS/cm BLCT4B00W2 BLCT5B00W0
400 V 3ph cylinder, conductivity 350 to 1250 μS/cm BLCT4C00W2 BLCT5C00W0
Electrode and gasket kit 400 V 3ph cylinder, conductivity 75 to 350 μS/cm KITBLCT4B2 KITBLCT5B2
400 V 3ph cylinder, conductivity 350 to 1250 μS/cm KITBLCT4C2 KITBLCT5C2
Gasket and fi lter kit KITBLC4FG0 KITBLC5FG0
Tab. 11.g
11.4 Cleaning and maintenance of the cylinder
Replacement
Important: the cylinder must be only be replaced by qualifi ed
personnel, and with the humidifi er unplugged from the power
supply.
In normal conditions, the disposable cylinders should be replaced after
one year (or 2500 hours of operation, if cleaned periodically), while the
openable cylinders last 5 years (or 10,000 hours of operation, if cleaned
periodically). They must be replaced immediately – even before the
specifi ed intervals – if any anomalies occur. For example, when the lime
scale inside the cylinder prevents the correct fl ow of electric current.
The cylinder must undergo periodical preventive maintenance by
Fortnightly visual and be replaced either when depleted (i.e., full of lime-
scale) or when its lifetime has expired as indicated in the manual or when
any anomalies occur. A non-exhaustive list of reasons for replacement is:
There is too much lime-scale inside the cylinder with electrodes fully
covered and (almost) touching each other: this can be seen by looking
into the cylinder through the steam outlet or by opening it if it is an
openable cylinder. Comment: it is normal that cylinders fi ll with lime-
scale because this is naturally contained in the supply water. Filling
with lime-scale is not an anomaly, however, when full of lime-scale, the
cylinder must be replaced