7. USER MENU
From the main screen press:
PRG to access the main menu,
ENTER to select and access the menu user.
User menu screens:
1. Alarm thresholds
2. System clock
3. Enable scheduler
4. Defi ne time zones
5. Weekly scheduler
6. Scheduled setpoint
7.1 Alarm thresholds
parameter par name. range default UOM
Main probe alarm
thresholds
High alarm
0 to 100.0 100.0
%
Low alarm
0 to 100.0 0.0
%
Limit probe alarm
thresholds
High alarm
0 to 100.0 100.0
%
Alarm delay
0 to 999 0
min
7.2 System clock
Used to set the timed activation of the humidifi er
parameter range
hour / min
0 to 23 / 0 to 59
day
1 to 31
month
1 to 12
year
00 to 99
format
dd/mm/yy - mm/dd/yy
week day
Sunday to Saturday
7.3 Enable scheduler
Enable control of the time bands and the set points
parameter enable
scheduler On/Off
YES / NO
variable set point
YES / NO
When the time bands are set, the display shows the symbol
7.4 Setting the time bands
Note: this screen is visible if scheduler ON/OFF” has been enabled
(see the enable scheduler screen).
Set the intervals for the operation of the humidifi er over a 24h period
(one day):
time bands
ON OFF
P1 P1-1 09:00 13:00
P1-2
14:00 21:00
P2 14:00
21:00
P3
always ON
P4
always OFF
Parameters P1 to P4 can be used set how many times steam production
is enabled/disabled over a 24h period:
P1 Two daily ON time bands
0 24h
ON
P1-1 P1-2
OFF OFF OFFON
P2 Individual ON time band
0 24h
P2
OFF OFFON
P3 Always ON
0 24h
ON
P4 Always OFF
0 24h
OFF
Fig. 7.1
7.5 Weekly scheduler
Note: this screen is visible if “scheduler ON/OFF” has been enabled
(see the enable scheduler screen).
Set the weekly operation of the humidifi er, using parameters P1 to P4
(confi gured in the previous screen)
parameter type of time band
Monday
P1,...,P4
Tuesday
P1,...,P4
Wednesday
P1,...,P4
Thursday
P1,...,P4
Friday
P1,...,P4
Saturday
P1,...,P4
Sunday
P1,...,P4
7.6 Scheduled set points
Note: this screen is visible if “variable set point has been enabled (see
the enable scheduler screen).
Set diff erent levels of set points throughout the day (24h):
parameter
ON SETP.
hours %rH
Z1
00:00 0.0...
Z2
00:00 0.0...
Z3
00:00 0.0...
Z4
00:00 0.0...
Parameters Z1 to Z4 can be used to confi gure up to four diff erent
temperature set points at diff erent times of a day (parameters Z1, Z2, Z3,
Z4).
Z1 Z2
20°C
50°C
30°C
Z3 Z4
0 24h
Fig. 7.b
By setting the daily and “variable set point” time bands, steam production
can be programmed according to the needs of the utility.
Note:
during the “OFF” time band, the humidifi er is NOT actually off , but
rather steam production is temporarily disabled, even when setting
manually;
the daily time bands have priority over the “variable set point bands.
For example, setting P4 each Monday (humidifi er off ), parameters
Z1, Z2, Z3, Z4 (diff erent set point values) will not be observed, as the
humidifi er is not programmed to operate on that day.