“UEX-PLUS” +0300040EN - rel. 1.4 - 25.09.2015
installeruserservice
49 R/W cylinder 1: reset of the hour counter
50 R/W cylinder 2: reset of the hour counter
51 R/W alarms reset
52 R/W cylinder 1: manual drain: 1 = on, 0 = off
53 R/W cylinder 2: manual drain: 1 = on, 0 = off
54 R/W cylinder 1: cleaning cycle: 1 = on, 0 = off
55 R/W cylinder 2: cleaning cycle: 1 = on, 0 = off
79 R alarm SERIALE OFFLINE
80 R/W Enabling control supervisor (1=enabled)
81 R/W Enabling ON-OFF from supervisor (1=enabled)
“I”
read (R)/
write (W)
integer variables (Modbus®: REGISTERS)
CAREL Modbus®
1 129 R high part sw version
2 130 R low part sw version
3 131 R day sw version
4 132 R month sw version
5 133 R year sw version
6 134 R sw release type
7 135 R sw release number
8 136 R
humidifi er status
0 = on duty; 1 = alarm(s) present; 2 = disabled via network; 3 = disabled by timer; 4 = disabled by remote on/off ;
5 = disabled by keyboard; 6 = manual control; 7 = no demand
9 137 R conductivity reading
10 138 R/W manual force conductivity value
11 139 R
cylinder 1: working phase
0 = not active; 1 = softstart; 2 = start; 3 = production at steady state; 4 = reduced production
5 = production delayed stop; 6 = full fl ush; 7 = Fast Start; 8 = Fast Start_FT (Foam Test); 9 = Fast Start_HW (Heating
Water - waiting to boil)
12 140 R
cylinder 1: status
0 = no production; 1 = start of evaporation cycle; 2 = water fi ll; 3 = steam production in progress;
4 = water drain (decision to open the contactor; drain pump still stopped); 5 = water drain (drain pump running);
6 = water drain (drain pump stopped; contactor closing, if open); 7 = humidifi er blocked
8 = long-term-inactivity full drain; 9 = fl ushing of the hydraulic circuit; 10 = full drain by manual or network request;
11 = automatic management of lack of supply water; 12 = total periodic drain
13 141 R
cylinder 2: working phase
0 = not active; 1 = softstart; 2 = start; 3 = production at steady state; 4 = reduced production; 5 = production delayed stop; 6
= full fl ush
14 142 R
cilindro 2: status
0 = no production; 1 = start of evaporation cycle; 2 = water fi ll; 3 = steam production in progress;
4 = water drain (decision to open the contactor; drain pump still stopped); 5 = water drain (drain pump running);
6 = water drain (drain pump stopped; contactor closing, if open); 7 = humidifi er blocked
8 = long-term-inactivity full drain; 9 = fl ushing of the hydraulic circuit; 10 = full drain by manual or network request;
11 = automatic management of lack of supply water; 12 = total periodic drain
15 143 R/W
regulation type:
0 = on/off ; 1 = slave 0-100%; 2 = slave 0-100% + limit probe; 3 = %rh control with external probe without limit probe
4 = %rh control with external probe + limit probe; 5 = temperature control
16 144 R/W
room probe/ext. regulator: type of signal
0 = 0-1 v; 1 = 0-10 v; 2 = 2-10 v; 3 = 0-20 ma; 4 = 4-20 ma; 5 = ntc carel standard
17 145 R/W limit probe: type of signal: 0 = 0-1 V; 1 = 0-10 V: 2 = 2-10 V; 3 = 0-20 mA; 4 = 4-20 mA; 5 = NTC CAREL standard
18 146 R/W maintenance time-out
19 147 R/W periodical fl ush: period
20 148 R/W inactivity drain: time-out
21 149 R/W conductivity warning: threshold
22 150 R/W conductivity alarm: threshold
23 151 R/W tuning of dilution frequency: parameter b8
24 152 R/W tuning of dilution duration: parameter b9
25 153 R system timer: hour
26 154 R system timer: minute
27 155 R system timer: day
28 156 R system timer: month
29 157 R system timer: year
30 158 R system timer: week day
31 159 R/W
system timer: week day (can be edited for updating the sistem timer!)
0 = monday; 1 = tuesday; 2 = wednesday; 3 = thursday; 4 = friday; 5 = saturday; 6 = sunday
32 160 R/W system timer: hour (can be edited for updating the sistem timer!)
33 161 R/W system timer: minute (can be edited for updating the sistem timer!)
34 162 R/W system timer: day (can be edited for updating the sistem timer!)
35 163 R/W system timer: month (can be edited for updating the sistem timer!)
36 164 R/W system timer: year (can be edited for updating the sistem timer!)
37 165 R cylinder 1: hour counter
38 166 R cylinder 2: hour counter
39 167 R voltage type (v): 0 = 200; 1 = 208; 2 = 230; 3 = 400; 4 = 460; 5 = 575
40 168 R/W humidifi er type
52 180 R lista modelli umidifi catori
53 181 R/W
parameter Installer/Supervisor/Supervisor connect/Reg. from BMS: sending analog signal control(0-1000, temper: tenths of
°C/°F, umid: tenths of rH%)
54 182 R/W parameter Installer/Supervisor/Supervisor connect/O ine al. Delay: time delay for alarm SERIAL OFFLINE (seconds)