4.8 — 06CC (50 to 99 Cfm) 3 Phase Electrical Specifications
LEGEND
LRA – Locked Rotor Amps PW – Part Winding (Start)
MH – Must Hold Amps RLA – Rated Load Amps
MT – Must Trip Amps XL – Across-the-Line (Start)
* Refer to revised Bulletin 03T-2 for recommended motor protection.
NOTES:
1. Compressor must-trip (M.T.) amps and RLA values are maximum figures.
2. LRA values for PW second winding = 1/2 the LRA-XL value.
3. 3-Pole XL circuit breakers shown, other 3-Pole XL alternates and 6-Pole PW breakers available. Terminal lugs for circuit breakers available in pack-
age 06EA660152.
4. RLA value shown is determined by: circuit breaker must trip value ÷ 1.40. Use this recommended (and minimum) RLA value to determine name
plate stamping, minimum contactor sizing, and wire sizing. RECOMMENDED RLA FOR 06CC COMPRESSOR EQUALS: MUST-TRIP (M.T.) OF
CARLYLE APPROVED OVERCURRENT DEVICE BEING USED ÷ 1.40.
5. Compressor operating amps at any specific condition can only be determined from a performance curve.
6. Ohm values for resistance are approximate and shown for reference purposes only. Motors from different vendors and motors of different efficien-
cies can differ up to 15% from data shown.
COMPRESSOR MOTOR DATA CIRCUIT BREAKER DATA*
Compressor
Model
VOLT
MAX
kW
HP
SEE NOTE 1 SEE NOTE 2
MOTOR
WINDING
RESISTANCE
(Ohms)
SEE NOTE 3
M.H. M.T. LRA
SEE
NOTE 4
Max. Must
Trip Amps
LRA-XL
LRA-PW
(First
Winding)
Recomm
Circuit Breaker
Part No.
RLA with
Listed
Breaker
06CC550F201
550J201
550E201
460
575
203/230/460
22.0 15
32
27
68/32
142
98
283
85
59
170
2.8
1.8
0.44/0.22
HH83XB414
XB438
XB455/XB414
27
23
59
32
27
68
145
86
24
5
23
19
49
06CC665F201
665J201
665E201
460
575
203/230/460
25.3 20
50
38
100/50
173
120
345/173
104
72
207
2.2
1.3
0.32/0.16
HH83XB437
XB461
XB376/XB437
43
33
73
50
38
85
176
124
333
36
27
61
06CC675F201
675J201
675E201
460
575
203/230/460
25.3 20
50
33
100/50
173
120
345/173
104
72
207
2.2
1.3
0.32/0.16
HH83XB437
XB422
XB378XB437
43
34
77
50
40
89
17
6
120
365
36
29
64
06CC899F201
899J201
899E201
460
575
203/230/460
39.1 30
58
58
141/73
253
176
506/253
152
106
304
1.3
0.88
0.22/0.11
HH83XB432
XA430
XC406/XB432
63
50
122
73
58
141
240
168
464
52
41
101
ALLOWABLE OPERATING RANGES
NOMINAL
VOLTAGE
MAXIMUM MINIMUM
208/230
460
575
400 (50 Hz)
200 (50 Hz)
254
529
661
460
230
187
414
518
342
180